17
2.4.1 Connecting the AC Power
WARNING!
To reduce the risk of electrical shock, make sure that all power has been turned off or disconnected
prior to attempting to connect power to the Power Supply.
Apply the AC Power BEFORE connecting the batteries to the Panel!
Provide the Fire Alarm Control Panel with a dedicated AC Circuit rated 15 Amps.
Refer to Figure 2.1 for wiring diagram.
1. Enter Power Cable into Cabinet via left side knock out hole.
2. Attach the brown (live) wire from the source to terminal
“Line” (USA use color black wire).
3. Attach the blue (neutral) wire from the source to the “Neutral” terminal (USA use color white wire).
4. Attach the ground wire from the source to the “GD” terminal block (USA use color green wire).
Figure 2.1
P1
Battery
Fault
GND wire
NEUTRAL
LIVE
Normal
+ -
GND
Factory fitted
NO NOT REMOVE
The GND cable must
be connected to this
point
+
-
Содержание MA-1000
Страница 2: ...1 ...
Страница 3: ...2 ...
Страница 15: ...14 MA 1000 ...
Страница 17: ...16 Peripheral Devices ...
Страница 62: ...61 Appendix 4 9 MA 1000 Site Installer User Manual ...
Страница 63: ...62 ...
Страница 71: ...70 ...
Страница 76: ...75 FIGURE 12 Allocated devices list ...
Страница 80: ...79 FIGURE 14 Allocated List ...
Страница 84: ...83 6 Select Delete Device button FIGURE 19 Select Device ...
Страница 88: ...87 Save as TXT format ...
Страница 89: ...88 Panel outputs Save as EXEL format ...
Страница 90: ...89 2 2 13 History Events 1 Select Read History button FIGURE 23 Read History FIGURE 23 Save Event list ...
Страница 91: ...90 FIGURE 21 View Event 2 History will display automatically in the default browser ...
Страница 93: ...92 4 Select Add panel or Delete panel 5 Select Close to apply ...
Страница 98: ...97 ...
Страница 103: ...102 Fig 1 ...
Страница 105: ...104 Appendix 4 12 Detectors UL Certifications ...
Страница 106: ...105 ...
Страница 107: ...107 ...