76
2.2.8 Configuring MA-1000 Onboard Outputs
To set the operating condition of onboard output circuits, select the
NACs
or
Relays
button, as indicated below in
FIGURE 13
: -
SILENCE
When the Silence key is pressed the NAC turn off.
FIRE
NAC to turn on when a fire alarm condition exists
AUX Continuous
Power supply 24VDC.
AUX Resettable
Power supply 24VDC resettable (lost power for 2 sec after reset).
Door Magnets
A steady 24VDC in an ALARM condition the AUX changes state to OFF until
RESET.
SUPERVISORY
NAC turns on when a supervisory condition exists.
CADENCE
NAC Cadence is where you choose the NAC type ON, March code,
ANSI S-3-41, Single stroke BI, California code, Wheelock.
Delay
Delay time 0-120 sec to trigger Nac On when FIRE NAC is selected.
Each step 10
–sec.
Timer
Timer 0-120 sec to trigger Nac Off when FIRE NAC is selected.
Each step 10
–sec.
Содержание MA-1000
Страница 2: ...1 ...
Страница 3: ...2 ...
Страница 15: ...14 MA 1000 ...
Страница 17: ...16 Peripheral Devices ...
Страница 62: ...61 Appendix 4 9 MA 1000 Site Installer User Manual ...
Страница 63: ...62 ...
Страница 71: ...70 ...
Страница 76: ...75 FIGURE 12 Allocated devices list ...
Страница 80: ...79 FIGURE 14 Allocated List ...
Страница 84: ...83 6 Select Delete Device button FIGURE 19 Select Device ...
Страница 88: ...87 Save as TXT format ...
Страница 89: ...88 Panel outputs Save as EXEL format ...
Страница 90: ...89 2 2 13 History Events 1 Select Read History button FIGURE 23 Read History FIGURE 23 Save Event list ...
Страница 91: ...90 FIGURE 21 View Event 2 History will display automatically in the default browser ...
Страница 93: ...92 4 Select Add panel or Delete panel 5 Select Close to apply ...
Страница 98: ...97 ...
Страница 103: ...102 Fig 1 ...
Страница 105: ...104 Appendix 4 12 Detectors UL Certifications ...
Страница 106: ...105 ...
Страница 107: ...107 ...