Virtual Channels 

The ioLogik E2262 provides virtual channels so you can easily determine the average or deviation values for 

any attached temperature sensor. A virtual channel can operate in Average Mode or Deviation Mode. In 

Average Mode, up to 8 physical channels are selected and the virtual channel reports the average value of the 

selected channels. In Deviation mode, two physical channels are selected and the virtual channel reports the 

difference between the channels. 

When using virtual channels, if there are errors on any of the selected physical channels, that channel’s 

readings will simply be ignored. You can refer to the LED indicators to see if any errors are encountered with 

any of the physical channels. 

Note that virtual channels only support temperature units and cannot be used with resistance units. Any 

channel that is connected to a mV voltage input will be treated as an error channel. 

Calibration 

The ioLogik E2262 allows you to calibrate the TC sensor by user. In each channel configuration section, click 

“Calibration” and then follow the onscreen instructions to start the TC sensor calibration. Each calibration needs 

about 20 seconds (per channel). Note that you can press “Reset to default” on the Navigation Panel to reload 

the factory default value and ignore the user calibrated value. The default value is calibrated in the factory and 

is stored in the device. 

 

Alias Name 

Click the Alias Name tab to customize the channel name. You may use names with up to 16 characters. If you 

already set the Alias Name on I/O Configuration page, the channel name will appear on Click&Go, Active 

message, and Web. 

 

 

 

Содержание ioLogik E2210

Страница 1: ...ioLogik E2200 Series User s Manual Edition 6 5 November 2016 www moxa com product 2016 Moxa Inc All rights reserved...

Страница 2: ...s to this manual or to the products and or the programs described in this manual at any time Information provided in this manual is intended to be accurate and reliable However Moxa assumes no respons...

Страница 3: ...guring the Host Computer s IP Address 2 4 Activating ioAdmin and Connecting to the ioLogik 2 5 Adding More I O Channels 2 8 Setting the RS 485 Baudrate 2 9 I O Wiring Diagrams 2 9 Using ioAdmin to Imp...

Страница 4: ...ernet Configurations 5 4 RS 485 Settings 5 4 I O Settings 5 5 DI Channels 5 5 DO Channels 5 6 AI Channels 5 8 Alias Name 5 8 AO Channels 5 9 Relay Output Channel 5 9 Relay Count Motoring 5 10 Alias Na...

Страница 5: ...42 E 3 ioLogik E2260 E 3 ioLogik E2262 E 4 F Accuracy F 1 Calibration F 1 Simple Verification at Your Site F 1 Verification with RTD Sensor F 1 Verification with Precision Resistor F 1 G CGI Commands...

Страница 6: ...duct Key Features and Highlights Package Checklist Product Model Information Product Selection Guide Product Specifications Common Specifications ioLogik E2210 Specifications ioLogik E2212 Specificati...

Страница 7: ...rnet Remote IO with 8 DIs 8 DOs 4DIOs 10 to 60 C operating temperature ioLogik E2214 Ethernet Remote IO with 6 DIs 6 relays 10 to 60 C operating temperature ioLogik E2240 Ethernet Remote IO with 8 AIs...

Страница 8: ...els is 10 to 60 C The operating temperature for wide temperature models is 40 to 75 C Digital Inputs Selectable DIO Digital Outputs Relay Outputs Analog Inputs Analog Outputs RTD Inputs TC Inputs E220...

Страница 9: ...ating Temperature Standard Models 10 to 60 C 14 to 140 F Wide Temp Models 40 to 75 C 40 to 167 F Storage Temperature 40 to 85 C 40 to 185 F Ambient Relative Humidity 5 to 95 non condensing Altitude Up...

Страница 10: ...to GND On 0 to 3 VDC Off 10 to 30 VDC Common Type 12 points per COM Counter Frequency 900 Hz Digital Filtering Time Interval Software selectable Digital Output Type Sink I O Mode DO or Pulse Output Pu...

Страница 11: ...Contact DI to GND On 0 to 3 VDC OFF 10 to 30 VDC Common Type 6 points per COM Counter Frequency 900 Hz power off storage Digital Filtering Time Interval Software selectable Digital Output Type Sink I...

Страница 12: ...power off storage Digital Filtering Time Interval Software selectable Relay Output Type Form A N O power relay Contact Current Rating Inductive Load 2 A 30 VDC 250 VAC 110 VAC Resistive Load 5 A 30 V...

Страница 13: ...ples sec for current Per channel 1 25 samples sec for voltage 0 75 samples sec for current Single channel 1 25 samples sec for voltage 0 75 samples sec for current Input Impedance 900K ohms min Built...

Страница 14: ...nt Input 120 ohms Digital Input Sensor Type Wet Contact NPN or PNP and Dry Contact I O Mode DI or event counter Dry Contact On short to GND Off Open Wet Contact DI to GND On 0 to 3 VDC Off 10 to 30 VD...

Страница 15: ...ms Sampling Rate 12 samples sec all channels Resolution 0 1 C or 0 1 ohm Accuracy 0 1 FSR 25 C 0 3 FSR 10 and 60 C 0 5 FSR 40 and 75 C Input Impedance 625K ohms Digital Output Type Sink I O Mode DO or...

Страница 16: ...on 35 to 35 VDC power off 25 to 30 VDC power on Sampling Rate 12 samples sec all channels Resolution 16 bits Accuracy 0 1 FSR 25 C 0 3 FSR 10 and 60 C 0 5 FSR 40 and 75 C Input Impedance 1 M ohms Digi...

Страница 17: ...ioLogik E2200 Series Introduction 1 12 Physical Dimensions Without LCM Unit mm With LCM Unit mm...

Страница 18: ...lip to hold the RESET button down for 5 sec The RDY LED will turn red as you are holding the RESET button down The factory defaults will be loaded once the RDY LED turns green again At this point you...

Страница 19: ...Red Serial port connected Blinking Data sending and receiving Ethernet Off Ethernet port not connected Amber 10 Mbps connected Green 100 Mbps connected Blinking Data sending and receiving DI Off DI st...

Страница 20: ...tallation Connecting the Power Grounding the Unit Software Installation Restore Factory Defaults Connecting to ioAdmin via Ethernet Configuring the Host Computer s IP Address Activating ioAdmin and Co...

Страница 21: ...guration and management of ioLogik E2200 products and connected I O devices ioAdmin can be used to monitor and configure ioLogik E2200 products from anywhere on the network Some settings may also be c...

Страница 22: ...eviously configured ioLogik is to reset it to the factory default using the RESET button see Chapter 1 You can then use the ioAdmin utility to configure the ioLogik NOTE If the host computer has multi...

Страница 23: ...or initial configuration it is strongly recommended to use a direct connection between the ioLogik E2200 device s RJ45 Ethernet console port and the host computer rather than remotely over the network...

Страница 24: ...dialog window will appear Click Start Search to begin searching for your unit Once the ioLogik has been detected modify the settings as needed for your network environment and then restart the device...

Страница 25: ...o reboot the corresponding device with its new IP address and then click the Re Search button to refresh the list of IP address conflicts detected by ioAdmin 4 Log in as administrator For full access...

Страница 26: ...in supports four viewing options for the navigation panel If you select Sort by Active OPC Server the ioLogik will appear in the Active OPC Server group Simultaneously the same devices will be shown u...

Страница 27: ...additional analog channels can be added by using the ioLogik R2140 ATTENTION Multiple ioLogik E2200 R2140 units can be snapped together as part of the same RS 485 network But when connecting the powe...

Страница 28: ...ik E2200 series supports Unit IDs up to 247 for Modbus devices the highest Unit ID on the ioLogik R2140 is 99 Setting the RS 485 Baudrate The RS 485 port on the ioLogik E2200 series is reserved for co...

Страница 29: ...ut A varistor can serve as a contact protection circuit where the parallel circuit connects with the load NOTE A load in a circuit schematic is a component or portion of the circuit that consumes elec...

Страница 30: ...her DI channels in the group i e DIO 4 and DIO 5 Likewise if a PNP sensor is connected to DIO 6 then only PNP sensors can be connected to the other DI channels in the group i e DIO 10 and DIO 11 Using...

Страница 31: ...ng ioAdmin 3 10 or above especially if earlier versions of ioAdmin have been installed and then removed Import System Config Select this command to load a configuration for the selected ioLogik from a...

Страница 32: ...Links Navigation Panel Main Window Sync Rate Status Status Bar ioAdmin Administrator Functions I O Configuration Tab Administrator Server Settings Tab Administrator Network Tab Firmware Update Tab Wa...

Страница 33: ...O statuses Use active message monitoring Configure Click Go local control logic Upgrade the firmware Restart the ioLogik Restore factory default settings On line Wiring Guide For added convenience a...

Страница 34: ...main screen of the ioAdmin utility defaults to the I O Configuration tab which displays a figure of your ioLogik device with the status of each of its I O channels The other tabs on the main screen ta...

Страница 35: ...in the navigation panel You can also import a list into ioAdmin When importing exporting a device list you will be prompted to select which ioLogik on the list needs to be imported or exported When a...

Страница 36: ...u can search for ioLogik devices by type IP address range or model name Click Start Search to start searching and the search results will be shown at the bottom of the window Select auto search type S...

Страница 37: ...ration is used to adjust how often the ioLogik is polled for device status by the ioAdmin utility The current rate is displayed on the status bar at the bottom of the window Note The higher sync rates...

Страница 38: ...lve connecting to ioLogik R series devices Active Message Listen Port This operation specifies the port number to use for Active Messages If your network uses a firewall you can coordinate this settin...

Страница 39: ...Using ioAdmin 3 8 Sort The Sort menu allows the Devices list in the navigation panel to be sorted by connection model location or Active OPC Help In the Help menu you can view wiring guides and infor...

Страница 40: ...access the wiring guide by right clicking the ioLogik figure in the I O Configuration tab Select Wiring Guide in the submenu to open a help file showing the unit s wiring information and electrical ch...

Страница 41: ...cation Sort by Active OPC Server NOTE The default location is Empty If you do not specify the location for the ioLogik E2200 the navigation panel will group all Empty locations together Navigation Pan...

Страница 42: ...rget must be disconnected first to use this command Restart System Select this command to restart the selected ioLogik Reset to Default Select this command to reset all settings on the selected ioLogi...

Страница 43: ...O Configuration tab shows the status of every I O channel This is the default tab when you first open ioAdmin Input channels are listed on the left and output channels are listed on the right Server I...

Страница 44: ...ions section later on in this chapter for details Message Monitor Tab The Message Monitor tab will display any TCP UDP Active Messages reported by the ioLogik E2200 series When you install the unit fo...

Страница 45: ...ired whenever you start up ioAdmin or boot up restart the ioLogik When you install the ioLogik for the first time the password will be blank and you can simply click Login Additional functions will av...

Страница 46: ...ttings 1 Configuring Analog Input Channels 2 Configuring Analog Output Channels 3 Configuring DIO Channels 4 Configuring Digital Input and Event Counter Channels 5 Configuring Digital Output and Relay...

Страница 47: ...t all channels at the same time by selecting the Apply to all channels checkbox To increase the sampling rate disable any unused AI channels by deselecting the Enable Channelcheckbox Select the Enable...

Страница 48: ...ould be no need to wait for a higher temperature reading before responding Instead you can cut off the values beyond 17 mA and convert it to a proprietary level of danger such as Level 5 2 Auto Scalin...

Страница 49: ...is powered on The Power On Settings field uses raw data values If you do not know how to translate the raw data values into real values use the Test function for assistance Safe Status Settings Use th...

Страница 50: ...ering value V mA You may use this as a guide when entering values for the Power On and Safe Status settings Alias Name Click the Alias Name tab to customize the channel name You may use names with up...

Страница 51: ...ogik E2200 unit is turned on each DIO channel will be configured to act as either a DI or DO channel according to the Power On Settings To switch between DI and DO channel operation select the desired...

Страница 52: ...0 5 ms A DI channel can be set to DI or Event Counter mode In DI mode the specifications are as follows Type ON OFF Dry contact Short to GND Open Wet contact 0 to 3 VDC 10 to 30 VDC In Event Counter m...

Страница 53: ...ified in multiples of 0 5 ms for Digital Output 1 5 s for Relay output with a maximum setting of 65 535 For digital output you would enter 1000 for a width of 500 ms If the OFF width value is 5000 and...

Страница 54: ...ut channel has been used In general each relay output channel can be used an average of 1 000 000 times Users can monitor these counts to see when the module should be replaced or to switch to a diffe...

Страница 55: ...ut If the Host Connection Watchdog is not enabled then the DO Relay Output channel status will remain unchanged during a network disconnection ATTENTION The Host Connection Watchdog is disabled by def...

Страница 56: ...to 310 1 to 310 1 to 310 100 to 31000 PT50 0 00385 200 to 850 C 328 to 1562 F 2000 to 8500 PT100 0 00385 200 to 850 C 328 to 1562 F 2000 to 8500 PT200 0 00385 200 to 850 C 328 to 1562 F 2000 to 8500 P...

Страница 57: ...d physical TC input Thermocouple channels each supporting up to 8 different types including J K T E R S B N types and mV voltage inputs The TC channels are numbered from channel 0 to channel 7 Moreove...

Страница 58: ...h any of the physical channels Note that virtual channels only support temperature units and cannot be used with resistance units Any channel that is connected to a mV voltage input will be treated as...

Страница 59: ...time time zone and time server in the Server Settings tab ioAdmin supports long server names and a location description with up to 58 characters You may set up the Daylight Saving schedule by clicking...

Страница 60: ...wish to allow only certain IP addresses to have network access to the ioLogik and attached sensors Access will be granted only to the IP addresses that you list in the Accessible IP screen Any reques...

Страница 61: ...period the ioLogik will send four packages to the server to check for TCP connection When the server does not response within the specified time period ioLogik will automatically release its modbus TC...

Страница 62: ...warning and activate the Safe Status settings for each DO channel and Event Counter channel By default the Watchdog is disabled To enable the Watchdog make sure that Enable Host Connection Watchdog is...

Страница 63: ...nformation on defining rules Click Go Logic changes do not take effect until the ioLogik E2200 series has restarted Click Upload to upload the logic values and restart the ioLogik E2200 After logging...

Страница 64: ...settings to take effect ioLogik E2240 ioLogik E2210 The Heartbeat Interval can be used to determine the connection status between the ioLogik and Active OPC Server and to ensure that the ioLogik is c...

Страница 65: ...et and the network between the ioLogik and Active OPC Server is down Active OPC Server will detect the stopped heartbeat and the Quality column will show BAD to indicate the loss of the connection The...

Страница 66: ...annel On to Off or Off to On for digital channels or percentage change for analog channels 2 To periodically update the status of the Active OPC Server specify a time interval after the Update per che...

Страница 67: ...o monitor network and I O devices with SNMP Network Management software It is useful in building automation and telecom applications Use these fields to enable SNMP and set the read and write communit...

Страница 68: ...the first time the ruleset will not have been defined yet so there will be no messages on the Message Monitor Panel When a ruleset has been defined and activated any TCP UDP messages that have been tr...

Страница 69: ...fying its Unit ID Restart System Select this command to restart the selected ioLogik You will need to be logged in as an administrator to use this command Reset to Default Select this command to reset...

Страница 70: ...WN 0 Off DO11_SAFE 0 Off AI00 5 4 20mA AI00_EN 1 AI01 3 10V AI01_EN 1 AI02 3 10V AI02_EN 1 AI03 3 10V AI03_EN 1 AI00_SCALEN 0 AI00_ACTmin 0 000 AI00_ACTmax 0 000 AI00_SCALmin 0 000 AI00_SCALmax 0 000...

Страница 71: ...he installation program will guide you through the installation process and install the software 2 Open ioEventLog After installation has finished run ioEventLog from Start Program Files MOXA IO Serve...

Страница 72: ...gh a firewall It will need to match the settings for the ioLogik server that is being monitored The Log Directory is where the log files will be stored The default directory is C Program Files Moxa io...

Страница 73: ...an view previously saved logs by selecting Open from the Log menu You will be prompted for the data that you wish to view The logs for the day that you select will be displayed in the Alarm Log Viewer...

Страница 74: ...Logic Basics Working with Rules I O Configuration Digital Input Mode Selection Digital Output Mode Selection Analog Input Mode Selection Alias Name Configuration Testing the I O Channels Defining Glo...

Страница 75: ...in a rule and you can define up to 24 rules Supported actions include sending SNMP traps or TCP UDP messages to up to 10 hosts at a time Click Go Function Comparison Table by Product Line Product Line...

Страница 76: ...on go to the Click Go Logic panel It should appear as below Click Go Logic Panel 1 Global Variable In this field you can assign a Global Variable for the set of rules 2 Logic Name In this field you ca...

Страница 77: ...a real time text based summary of the rule that you are defining and provides a useful means of making sure that the rule is designed as you intended ATTENTION When configuring input and output contro...

Страница 78: ...the ON OFF status When Lo to Hi is selected the counter value increases when the attached switch is pushed When Hi to Lo is selected the counter value increases when the switch is pushed and released...

Страница 79: ...en logged in as administrator double click on a channel on the I O Configuration panel to configure that channel s settings A window will open with configuration options for that channel Each AI chann...

Страница 80: ...g Testing the I O Channels Each I O channel can be tested and monitored individually When logged in as administrator double click on a channel in the I O Configuration panel to configure that channel...

Страница 81: ...Register Setting 2 Time Setting 3 SNMP Trap Server 4 Email Server 5 Active Message Server Internal Register Integer Settings Internal Register Integer is a flag that can be used with the Click Go logi...

Страница 82: ...interval before using a timer With the default state set to START the timer will start when the Click Go logic is activated Timer Number Initial State Configuration Timer Timer 0 to Timer 23 START STO...

Страница 83: ...contain a list of available e mail addresses for your network environment The e mail message defined in the Click Go logic will be sent to all addresses listed in the Receiver s list To add e mail ad...

Страница 84: ...ocol TCP or UDP and the message socket port must also be configured The active message defined in the Click Go logic will be sent to all addresses listed in the Message Recipient List Message Port TCP...

Страница 85: ...this field you can configure global variable rules 2 Logic Name In this field you can assign a name to the set of rules 3 Rule set In this area each rule s conditions actions and status are displayed...

Страница 86: ...cessed You will see a list of the rules in the current rule set on the main screen Double Click on a rule to open that rule s configuration window as shown in the following figure or double click on a...

Страница 87: ...al Register Float can be used as the comparison or throughput setting controlled by remote SCADA or a Modbus TCP program Relay CurRelayCNT x represents the current relay counts for the channel Max Val...

Страница 88: ...acked in a box so the Counter x should be reset every 10 counts Counter 1 10 Select the IF condition to Counter and click on the property button to enter the Counter Settings window AI AI refers to th...

Страница 89: ...the Timer function or to combine other input statuses together The Internal Register function also allows a PC to control the ioLogik s local output when the remote output is controlled by a Click Go...

Страница 90: ...hich helps the user indentify the relationship between rules In addition the Set Timer button will help define the default value for the Timer Schedule The Schedule function allows users to set a star...

Страница 91: ...N column you can specify up to 3 actions that will be performed when the IF conditions are satisfied 3 actions under the ELSE column will also be performed when the IF is NOT satisfied Possible action...

Страница 92: ...ESET ResetCNT x represents the number of the relay channel Internal Register Reg x represents the number of the internal register x 00 to 23 Trigger Value 0 to 255 Timer STOP START RESTART Timer x x 0...

Страница 93: ...e readings of a meter Select the THEN ELSE action to Counter and click on the property button to enter the Counter Settings window DO DO refer to the action of controlling the local digital output cha...

Страница 94: ...to Pulse Output and click on the property button to enter the Pulse Output Settings window AO Analog Output AO refers to the action of controlling the local Analog Output channels that react to the IF...

Страница 95: ...the first logic to the second one by specifying other actions in the THEN ELSE fields Values from 0 to 255 can be used here Select the THEN ELSE action for Timer and click on the property button to en...

Страница 96: ...in column indicates this Timer is also used in Rule 0 which helps the user identify the relationship between the rules In addition the Set Timer button can be used to define the default value of the...

Страница 97: ...tive Message In response to a proper IF condition the Active Message function sends a customized message to one or more IP destinations by TCP or UDP packets Select the THEN ELSE action for Active Mes...

Страница 98: ...ge Monitor as shown in the following screen shot When sending a message in HEX each HEX value must be separated by commas View the incoming message on the Message Monitor panel and select the HEX chec...

Страница 99: ...ive Message and e mail based on the same event but with different content you will need to use two separate logic entries one for the Active Message and one for the e mail SMTP server information incl...

Страница 100: ...eration will resume when it is turned back on allowing you to use the ioLogik for PC independent automation Rule set Management Bar When the rule set has been activated from the Click Go panel it will...

Страница 101: ...edge detection is not involved As long as the sensors remain on the required conditions are satisfied and the THEN actions will repeat at interval N DI 0 ON DI 1 ON DI 2 ON Relation between condition...

Страница 102: ...I 2 ON Relation between conditions AND OR IF conditions satisfied Repeat interval N A N A THEN action triggered Edge Detection for One Condition In this scenario the rule checks DI 0 for a change in s...

Страница 103: ...asic Settings Network Settings General Settings Ethernet Configurations RS 485 Settings I O Settings DI Channels DO Channels AI Channels Alias Name AO Channels Relay Output Channel Relay Count Motorin...

Страница 104: ...after making configuration changes The Submit button will be located at the bottom of every page that has configurable settings If you navigate to another page without clicking the Submit button your...

Страница 105: ...ins basic information about the ioLogik including the model name serial number firmware version MAC address and current IP address Basic Settings On the Basic Settings page you can set the ioLogik s s...

Страница 106: ...hdog will activate the Safe Status settings for each DO channel and Event Counter channel By default the watchdog is disabled To enable the Watchdog select Enable communication watchdog and set the ti...

Страница 107: ...Channel DI Channels On the DI Channels page you can view the status of each DI digital input channel Only DIO channels that are acting as DI channels will be displayed Click on a channel to see that...

Страница 108: ...ivate this function enable Power On Setting If Power On Setting is not enabled the channel will only start counting events when specified by a Modbus command or Click Go Logic rule You can control how...

Страница 109: ...mode or Pulse Output mode In DO mode output is either on or off In Pulse Output mode a configurable square wave is generated By default DO and Pulse Output channels are set to off when the ioLogik is...

Страница 110: ...inimum or maximum values recorded and displayed in the ioAdmin main window Auto Scaling can also help to eliminate high or low end extremes For example if 17 mA represents a dangerous high temperature...

Страница 111: ...us is controlled by the Host Connection Watchdog which is disabled by default If the Host Connection Watchdog is disabled the ioLogik E2240 will never enter Safe Status and your Safe Status settings w...

Страница 112: ...change to the channel s status when there is a network disconnection With the Watchdog enabled the Safe Status Setting determines whether the channel will turn off on or begin pulse output when there...

Страница 113: ...ng table is a list of supported sensor types and ranges Sensor Type Degree Count PT50 0 00385 200 to 850 C 2000 to 8500 PT100 0 00385 200 to 850 C 2000 to 8500 PT200 0 00385 200 to 850 C 2000 to 8500...

Страница 114: ...set the Alias Name You can click on each channel to enable or disable it or to configure the TC input mode When a channel has been disabled the sample rate of the remaining channels will be increased...

Страница 115: ...IP list is enabled a host s IP address must be listed in order to obtain access to the ioLogik You can add a specific address or range of addresses by using a combination of IP address and netmask as...

Страница 116: ...supports SNMP v1 v2c and V3 Simple Network Management Protocol to allow monitoring of network and I O devices with SNMP Network Management software Network Connection On the Network Connection page y...

Страница 117: ...g page you can save the ioLogik s configuration into a file for backup or for importing into another ioLogik server LCM If you have installed the optional LCM you can view the status and firmware deta...

Страница 118: ...n to a file when you have finished setting up your ioLogik Your configuration can then be easily imported back into the ioLogik This will be useful if the ioLogik has been reset to factory defaults du...

Страница 119: ...r Active OPC Server From Pull to Push Features of Active OPC Server One Click to Create Active Tags Faster More Accurate Data Collection than Traditional Pull Technology Active OPC Server Overview Ins...

Страница 120: ...ess control is an industry standard created with the collaboration of a number of leading worldwide automation hardware and software suppliers working in cooperation with Microsoft The standard define...

Страница 121: ...lso requires connected I O devices to use fixed IP addresses For applications running on a public network which usually means dynamic IPs or when portable wireless equipment is used there is no way to...

Страница 122: ...tes the headache of specifying individual target IP addresses I O channels and data formats while even eliminating any need for editing and importing configuration files Working from either of Moxa s...

Страница 123: ...architectures With Moxa s active technology advantage users can now instantly receive alarms and real time updates allowing for timely risk response Active OPC Server Overview Installing Active OPC S...

Страница 124: ...Navigation panel 4 Tag window 5 Log monitor 6 Status bar Menu Bar File From the File menu select Export I O Server List to export a list of the ioLogik servers currently displayed in the navigation p...

Страница 125: ...n and type model Expand All Device The Expand All Device option will expand all the devices in the Navigation panel Collapse All Device The Collapse All Device option will collapse all the devices in...

Страница 126: ...e DCOM Unregister OPC Server This operation cancels the registration of the DCOM components from the Windows system Network Interface Use this operation to select which network to use if the PC has mu...

Страница 127: ...device default 60 seconds Enable Auto Save Configuration When Auto Save is enabled Active OPC will automatically save the configuration when Access synchronizes DCOM Configuration This operation launc...

Страница 128: ...ollowing steps to create the tags 1 Check mark the Enable Active OPC checkbox 2 Type in the Active OPC server IP Address 3 Select that I O you would like to update 4 Specify the update timing 5 Click...

Страница 129: ...twork between the ioLogik and Active OPC Server is down Active OPC Server will detect the stop of the heartbeat and the Quality column will show BAD to indicate the loss of the connection The default...

Страница 130: ...ier field maintenance The LCM is hot pluggable and can be used to configure the network settings and display other settings When plugged in the LCM displays the ioLogik home page Other pages and infor...

Страница 131: ...the down button to view the submenus ioLogik E2242 server Enter this submenu to display information about the specific server you are viewing serial number name location e2242 f w ver lcm f w ver mod...

Страница 132: ...erwise the display will show the response time ioLogik E2242 save restart Enter this submenu to display the restart now submenu Enter the restart now submenu to display the restart option Press the ce...

Страница 133: ...rt Type Usage 68 UDP BOOTPC 68 UDP DHCP 69 UDP Export import file 80 TCP Web Server 161 TCP SNMP 502 TCP Modbus Communication 4800 UDP Auto search 9020 TCP Peer to Peer function 9000 TCP Active Messag...

Страница 134: ...Lo to Hi Counter Status Stop AI Mode 10 V AO Mode 4 to 20 mA DO Mode DO Safe Status Off Pulse Low Width 1 Pulse Hi Width 1 No of Pulses 0 continuous RTD Mode PT 100 Unit C TC Sensor Type K type TC Ena...

Страница 135: ...ble Wiring The following topics are covered in this appendix Device Wiring Diagrams Analog Input Analog Output Digital Input Dry Contact Digital Input Wet Contact RTD Input Wiring Thermocouple Input W...

Страница 136: ...ing Diagrams Analog Input Analog Output Digital Input Dry Contact ATTENTION When connecting the I O device to the ioLogik s dry contacts we strongly recommended connecting DI Com to the power of the e...

Страница 137: ...ioLogik E2200 Series Cable Wiring D 3 Digital Input Wet Contact NPN Type Sensors Connection PNP Type Sensors Connection Digital Output Sink Type...

Страница 138: ...ioLogik E2200 Series Cable Wiring D 4 Digital Output Sink Type...

Страница 139: ...ioLogik E2200 Series Cable Wiring D 5 RTD Input Wiring Structure 2 wire 3 wire...

Страница 140: ...ioLogik E2200 Series Cable Wiring D 6 Thermocouple Input Wiring Structure 2 wire...

Страница 141: ...E E Input and Output Terminal This appendix includes the pin outs of the all E2200 series products ioLogik E2210 ioLogik E2212 ioLogik E2214 ioLogik E2240 ioLogik E2242 ioLogik E2260 ioLogik E2262...

Страница 142: ...ioLogik E2200 Series Input and Output Terminal E 2 ioLogik E2210 I O left to right ioLogik E2212 I O left to right ioLogik E2214 I O left to right...

Страница 143: ...ioLogik E2200 Series Input and Output Terminal E 3 ioLogik E2240 I O left to right ioLogik E2242 I O left to right ioLogik E2260 I O left to right...

Страница 144: ...ioLogik E2200 Series Input and Output Terminal E 4 ioLogik E2262 I O left to right...

Отзывы: