ioLogik E2200 Series
Click&Go
4-29
Edge Detection for Two Conditions
In this scenario, the rule checks DI-0 and DI-1 for a change in status and DI-2 for status only. The repeat
interval will not have an effect if the AND relationship is used, because the two edge conditions can never be
sustained over a length of time. With the OR relationship, the IF conditions will be satisfied as long as DI-2 is
“on”, and the THEN actions will be triggered over interval N.
DI-0 = OFF to ON
DI-1 = OFF to ON
DI-2 = ON
Relation between
conditions
AND
OR
“IF” conditions
satisfied
Repeat interval
N/A
N/A
“THEN” action
triggered
Edge Detection for One Condition
In this scenario, the rule checks DI-0 for a change in status and DI-1 and DI-2 for status only. The repeat
interval will not have an effect if the AND relationship is used, because the edge condition for DI-0 can never
be sustained over a length of time. With the OR relationship, the IF conditions will be satisfied as long as DI-1
or DI-2 is “on”, and the THEN actions will be triggered over interval N.
DI-0 = OFF to ON
DI-1 = ON
DI-2 = ON
Relation between
conditions
AND
OR
“IF” conditions
satisfied
Repeat interval
N/A
“Timer = N sec”
“THEN” action
triggered
Содержание ioLogik E2210
Страница 17: ...ioLogik E2200 Series Introduction 1 12 Physical Dimensions Without LCM Unit mm With LCM Unit mm...
Страница 138: ...ioLogik E2200 Series Cable Wiring D 4 Digital Output Sink Type...
Страница 139: ...ioLogik E2200 Series Cable Wiring D 5 RTD Input Wiring Structure 2 wire 3 wire...
Страница 140: ...ioLogik E2200 Series Cable Wiring D 6 Thermocouple Input Wiring Structure 2 wire...
Страница 144: ...ioLogik E2200 Series Input and Output Terminal E 4 ioLogik E2262 I O left to right...