ioLogik E2200 Series
Using ioAdmin
3-25
Configuring RTD Input Channels
The ioLogik E2260 provides 6 fixed physical RTD input (Resistance Temperature Detector) channels, each
supporting up to 18 different types including PT50, PT100, JPT100, and more. The RTD channels are numbered
from channel 0 to channel 5. Channels 6 through 11 are virtual temperature channels that report running
averages or deviations of selected RTD channels.
Alias Names
Click the
Alias Name
tab to customize the channel name. You may use names with up to 16 characters. If you
have already set the Alias Name on the I/O Configuration page, the channel name will appear in Click&Go,
Active message, and Web.
The following table is a list of supported sensor types and ranges.
Sensor Type
Degree
Degree
Count
Resistance (1 to 2200)
1 to 2200 Ω
1 to 2200 Ω
10 to 22000
Resistance (1 to 1250)
1 to 1250 Ω
1 to 1250 Ω
20 to 25000
Resistance (1 to 620)
1 to 620 Ω
1 to 620 Ω
50 to 31000
Resistance (1 to 310)
1 to 310 Ω
1 to 310 Ω
100 to 31000
PT50, 0.00385
-200 to 850°C
-328 to 1562°F
-2000 to 8500
PT100, 0.00385
-200 to 850°C
-328 to 1562°F
-2000 to 8500
PT200, 0.00385
-200 to 850°C
-328 to 1562°F
-2000 to 8500
PT500, 0.00385
-200 to 850°C
-328 to 1562°F
-2000 to 8500
PT1000, 0.00385
-200 to 350°C
-328 to 662°F
-2000 to 3500
JPT100, 0.003916
-200 to 640°C
-328 to 1184°F
-2000 to 6400
JPT200, 0.003916
-200 to 640°C
-328 to 1184°F
-2000 to 6400
JPT500, 0.003916
-200 to 640°C
-328 to 1184°F
-2000 to 6400
JPT1000, 0.003916
-200 to 350°C
-328 to 662°F
-2000 to 3500
Ni100, 0.00618
-60 to 250°C
-76 to 482°F
-600 to 2500
Ni200, 0.00618
-60 to 250°C
-76 to 482°F
-600 to 2500
Ni500, 0.00618
-60 to 250°C
-76 to 482°F
-600 to 2500
Ni1000, 0.00618
-60 to 180°C
-76 to 356°F
-600 to 1800
Ni120, 0.00672
-80 to 260°C
-112 to 500°F
-800 to 2600
The status of attached sensors will be reported by the count value, which corresponds to the sensor ranges
shown above. For example, for a 100 mΩ resistor, a count value of 10 corresponds to a 1 Ω reading. M
oxa can
only guarantee accuracy within the ranges shown above. Be sure to verify the sensor type. Accurate readings
beyond these ranges cannot be guaranteed.
Содержание ioLogik E2210
Страница 17: ...ioLogik E2200 Series Introduction 1 12 Physical Dimensions Without LCM Unit mm With LCM Unit mm...
Страница 138: ...ioLogik E2200 Series Cable Wiring D 4 Digital Output Sink Type...
Страница 139: ...ioLogik E2200 Series Cable Wiring D 5 RTD Input Wiring Structure 2 wire 3 wire...
Страница 140: ...ioLogik E2200 Series Cable Wiring D 6 Thermocouple Input Wiring Structure 2 wire...
Страница 144: ...ioLogik E2200 Series Input and Output Terminal E 4 ioLogik E2262 I O left to right...