ioLogik E2200 Series
Click&Go
4-14
IF Conditions
IF conditions
are events that trigger
THEN/ELSE actions
. Under the
IF
column, you can set up to 3
conditions that must be satisfied for the actions under the
THEN/ELSE
column to take place. As soon as the
IF conditions are satisfied, the specified THEN/ELSE action is performed. For example, an alarm can be
activated when a door is opened. Use the pull downs to specify the conditions and units of measurement (e.g.,
DI-0=OFF).
IF conditions can be specified as follows:
IF Conditions
Operators
Remark
DI
ON, OFF, ON to OFF, OFF to ON, Change
DI-x represents the channel number
Counter
=, >, <, >=, <=, Change
Counter-x represents the channel number.
Max Counter Value: 4,294,967,295
AI
=, >, <, >=, <=
AI-x represents the number of the channel.
Max Value: Depends on the analog modes
or the result of scaling. Internal
Register(Float) can be used as the
comparison or throughput setting
controlled by remote SCADA or a
Modbus/TCP program.
Relay
=, >, <, >=, <=
CurRelayCNT-x represents the current relay
counts for the channel.
Max Value: 4,294,967,295
Internal Register
=
Reg-x represents the number of the internal
register.
x = 00 to 23 / Trigger Value: 0 to 255
Timer
TIMEOUT
Timer-x, x = 00 to 23
Max value: 4,294,967 seconds
Schedule
Time, Range and Recurrence
Host Connection
Fail
N/A
When Port 502 is disconnected, the function
will be activate
DI
DI
refers to the status of a digital input channel. Edge detection can be used to refine the conditions. For
example, the condition
DI-0=OFF
is satisfied for as long as DI-0 remains off. The condition
DI-0=ON to OFF
,
however, is only satisfied the instant the DI-0 turns off. The transition of the status change can also be handled
using “Change” operator so it will trigger the related action whether it is ON-to-OFF or OFF-to-ON.
Scroll to select DI and click on the property (
) button to enter the DI Settings window.
Содержание ioLogik E2210
Страница 17: ...ioLogik E2200 Series Introduction 1 12 Physical Dimensions Without LCM Unit mm With LCM Unit mm...
Страница 138: ...ioLogik E2200 Series Cable Wiring D 4 Digital Output Sink Type...
Страница 139: ...ioLogik E2200 Series Cable Wiring D 5 RTD Input Wiring Structure 2 wire 3 wire...
Страница 140: ...ioLogik E2200 Series Cable Wiring D 6 Thermocouple Input Wiring Structure 2 wire...
Страница 144: ...ioLogik E2200 Series Input and Output Terminal E 4 ioLogik E2262 I O left to right...