Operation
66
5.9 Advanced Menu (continued)
PNU 53807
Advanced
Trip Settings
↓
L1-L3-L2 Trip
Determines if supply phase
sequence is incorrect for motor
rotation.
On: Trips if the phase
sequence is L1-L3-L2.
Off: The unit will not trip
regardless of motor rotation.
Off
On
Off
Read/Write
PNU 53804
Advanced
Trip Settings
↓
Remote Start Trip
For safety reasons the Unit will
trip during some operations if
the remote start signal is
active.
On: Trips if the remote start
signal is active when the Unit
is powered up or a reset is
applied.
Off: The Unit will not trip and
may start unexpectedly if the
start signal is accidently left
active.
Off
On
On
Read/Write
PNU 53775
Advanced
Trip Settings
↓
Current Sensor Trip
Detects if the internal current
sensors have failed or reading
a very low level.
On: The Unit will trip if the
internal current sensors fail or
the current measured falls to a
very low level.
Off: Will continue to operate
even if the sensor has failed.
Measurements and overload
protection may be affected.
Off
On
Off
Read/Write
PNU 53782
Advanced
Trip Settings
↓
Fan Trip
Detects if the cooling fans
have failed.
On: The Unit trips if the cooling
fans fitted to the Unit fail.
Off : The unit will continue to
operate and is likely to trip on
a thermal trip as the heatsink
will not be sufficiently cooled
Off
On
On
Read/Write
Menu
Description
Min
Max
Default
Unit Reg. Type