Operation
58
5.9 Advanced Menu (continued)
Menu
Description
Min
Max
Default Unit Reg. Type
PNU 640
Advanced
Start Settings
Kick Start
Kick Start Pedestal
Percentage of the supply
voltage applied to the motor
during the 'kick' period.
Increase to provide more
torque If the load fails to break
away.
Decrease if the motor
accelerates too quickly.
30
80
75
%
Read/Write
PNU 8320
Advanced
Start Settings
↓
Contactor Delay
Time allowed for external
contactors to close.
Increase if contactors are
driven by buffer relays or
motor trips on phase loss
when start signal applied.
Decrease if response to start
signal needs to be improved.
20
60000
160
ms
Read/Write
PNU 7296
Advanced
Stop Settings
↓
Stop Time
The time taken to soft stop
from full voltage or the iERS
level to the 'Stop Pedestal'.
Normally set between 15 and
60 seconds. Actual time to get
to 'Stop Pedestal' depends on
the "Stop Current Limit Level".
If set too long the motor may
reach zero speed before the
end of the time set. Refer to
"Automatic End Stop".
0
300
0
s
Read/Write
PNU 896
Advanced
Stop Settings
↓
Stop Pedestal
Percentage of the supply
voltage applied to the motor at
the end of the soft stop.
Increase if the motor crawls at
the end of the soft stop.
Decrease if a greater soft-stop
effect is required at the end of
the ramp.
10
40
10
%
Read/Write
PNU 53791
Advanced
Stop Settings
Stop Current Limit
Stop Current Limit Trip
Selects trip or continue if the
stop current limit has been
active for too long.
On: The Unit will trip.
Off: The stop will continue
regardless of the motor current
level.
Off
On
Off
Read/Write