Operation
55
5.9 Advanced Menu (continued)
Menu
Description
Min
Max
Default Unit Reg. Type
PNU 20608
Advanced
Automatic Settings
↓
Automatic Stop Profile
Adjusts the response of the
"Automatic Stop"
Increase if the motor speed
doesn't drop quickly enough.
.
When the value is set to zero
the "Automatic Stop" is
effectively disabled
0
100
50
%
Read/Write
PNU 20416
Advanced
Automatic Settings
↓
Automatic End Stop
Automatically controls the "Stop
Time"
On : The ramp time is
shortened if the motor reaches
a very low speed before the end
of the "Stop Time"
Off: The ramp time " depends
on the "Stop Time" and "Current
Limit"
Off
On
Off
Read/Write
PNU 20480
Advanced
Automatic Settings
↓
Automatic Impact Load
Automatically controls the
maximum iERS saving level.
On : The maximum iERS saving
level ("BackStop" ) is reset to
maximum during each load
cycle.
Off : The saving potential may
be reduced on applications with
heavy load cycles. Such as
injection moulding machines.
Off
On
Off
Read/Write
PNU 20224
Advanced
Automatic Settings
↓
Auto Smooth Stop
Automatically controls the soft
stop to eliminate oscillations
that can occur towards the end
of the ramp
On : The soft stop is adjusted
when oscillations are detected.
Refer to "Auto smoothing Level"
Off : The soft stop is unadjusted
and torque fluctuations may
cause instability. This can often
occur in pumping applications.
Off
On
Off
Read/Write
PNU 20672
Advanced
Automatic Settings
↓
Auto Smoothing Level
Adjusts the response of the
"Automatic smoothing"
Increase to provide a greater
smoothing effect If there are
torque fluctuations that occur
during the soft stop.
When set to zero the smoothing
is effectively disabled.
10
100
50
%
Read/Write