Operation
111
5.13 Device Menu (continued)
Menu
Description
Min
Max
Default
Unit Reg. Type
PNU 16000
Device
Networks
Modbus Network
Settings
Address
Sets the Modbus station
number
1
32
1
Read/Write
PNU 16064
Device
Networks
Modbus Network
Settings
Baud Rate
Sets the serial
communications baud rate.
The available baud rates are
9600 19200 38400 57600 or
115200.
9600
115200
19200
Read/Write
PNU 16128
Device
Networks
Modbus Network
Settings
Parity
Sets the serial
communications parity bit.
The available parity options
are None Even Odd.
Also sets the stop bits. No
parity uses 2 stop bits. Odd or
even parity uses 1 stop bit.
None
Odd
Even
Read/Write
PNU 14080
Device
Networks
Modbus Network
Settings
Traffic LEDS
Allows the user to check the
state of the modbus
communication network.
Red LED receive. Green LED
Transmit.
On: The Red and Green LEDS
display the traffic on the
Modbus communications
network.
Off: The Red and Green LEDs
display the Unit status
information.
Off
On
Off
Read/Write
PNU -
Device
Networks
↓
Anybus
Anybus expansion module.
Only active with Anybus
module fitted.
Read Only