Operation
82
5.10 Input/Output Menu (continued)
Menu
Description
Min
Max
Default
Unit Reg. Type
PNU 9600
I/O
Analogue Inputs
↓
Analogue Input Type
Defines the function of the
analogue input (AI).
0-10V: The input voltage
varies from 0-10V.
4-20mA: The input varies from
4 to 20mA.
0 - 10V 4 - 20mA
0 - 10V
Read/Write
PNU 9664
I/O
Analogue Inputs
↓
Select Function
Allows the Analogue input to
be mapped to different
functions
The selected function will
change in proportion with the
input
By default the function will be
at its maximum when the input
is at it maximum
Off
End of
List
Off
Read/Write
PNU 9728
I/O
Analogue Inputs
↓
Scaling Level
Allows the selected function to
be scaled.
The selected function will
change in proportion with the
input.
The function will be at its
"Scaling Level" when the input
is at its maximum.
0
Max
value
Max
value
%
Read/Write
PNU 8960
I/O
Analogue Outputs
↓
Analogue Output Type
Defines the physical function
of the analogue output (AO).
0-10V: The output voltage
varies from 0 to 10V.
4-20mA: The output current
varies from 4 to 20mA.
0 - 10V 4 - 20mA
0 - 10V
Read/Write
PNU 9024
I/O
Analogue Outputs
↓
Select Function
Allows the Analogue output to
be mapped to different PNU
functions.
The output will change in
proportion with the selected
function.
By default, the output will be at
a maximum when the selected
function equals its maximum
value.
Off
End of
list
Off
Read/Write