6.2.2 Logging Operation 2 Trip (2601 – 2603)
Trip numbers that are in the range of 2601 to 2603 indicate that a process associated with the
logging has been affected in some way and has been unable to recover automatically.
•
The trip is turned ON and OFF via the “Logging Trip” (Advanced/Trips).
•
The default for this trip is OFF.
•
With the trip OFF, the logging function will temporarily be disabled if a continual failure is
detected.
•
When the trip is turned ON, it is reset using either the digital input or keypad or bus
command, depending on the control method set.
•
It is possible to reset this trip by cycling the control supply.
Code
#
Description
2601 The initialization of the event logging function has been unsuccessful for 20 consecutive
attempts.
2602 The event logging function has been unsuccessful for 20 consecutive attempts.
2603 The SD card could not be accessed after 20 consecutive attempts.