NET Concentrator System
®
NCS
- 97 -
Moore Industries-International, Inc.
www.miinet.com
4
System time has been set to default.
Reboot and set the clock.
0
Clock battery failed, or clock mode
failed (replace the clock battery or
the clock module).
Replace the clock battery or the
clock module.
2
Could not resolve time server hostname.
There is an error in the Time Server field on
the System Time webpage
1
SNTP system communications error.
3
System timed out waiting for response
from time server.
Verify the IP address of the time server being
used, and that it accepts SNTP queries
1
Input power failed, running on
BBM power
The BBM has detected (and has reported to the
Interface Module) that mains power has been
lost. Restore power before the battery is
completely discharged.
0
The Battery Backup Module’s
battery is bad
If there is no BBM connected, then both bits will be set. In this case, the following UI message will be displayed:
“(00/01) The Battery Backup Module is not present.”
Verify physical connection between BBM and
NCS Interface Module
4
I/O Wiring module type mismatch.
The ISaGRAF resource is expecting certain
module types, however different modules are
physically present. Either correct the resource,
or install the correct modules.
0
ISaGRAF has caused a system fault.
Reboot and check if the condition clears itself.
3
Reserved
N/A
2
Reserved
N/A
1
Reserved
N/A
6
One or more resources failed to
write data.
There is not enough room left in non-volatile
storage. Use the ISaGRAF webpage to
"Clear Retain Variables". If the problem is not
corrected after a power cycle, reduce the
number of variables configured as "retained"
5
One or more resources failed to restore
retained data.
(This error is normal the first time a resource
with retain variables is executed, or when the
variables in the dictionary are changed. If after
an ISaGRAF restart (or a reboot) the problem
persists, check the "Clock Battery Fail" bit in
the System Time Substatus register
BIT
Position Description
Troubleshooting
BIT
Position Description
Troubleshooting
BIT
Position Description
Troubleshooting
Appendix Table 16.
ISaGRAF Status Register Bit Positions
Appendix Table 15.
Battery Backup Module Status Register Bit Positions
Appendix Table 14.
Time Subsystem Status Register Bit Positions