NET Concentrator System
®
NCS
- 38 -
Moore Industries-International, Inc.
www.miinet.com
Master Start
– The coil/register in the NCS
to be used
as a source for writes and a destination for reads.
For queries that involve a range of coils/registers
this value corresponds to the first coil/register in that
range.
Fail Coil
– The coil in the Interface Module’s register
map where errors with the transfer are reported.
Following the execution of a transfer, a value of 1
written to the fail coil indicates that an error has
occurred with the transfer. Refer to *
Note
.
It is possible for multiple transfers to use the same fail
coil. In this case, any error in those transfers (logical
OR) will set the coil to true.
Enable Coil
– The coil in the Interface Module’s
register map that is used to control whether or not a
transfer should be executed. A value of zero in this
field means no enable coil is used (i.e. execution of
the transfer can not be inhibited). Refer to *
Note
.
It is possible to have multiple transfers use the same
coil, thereby allowing a group of transfers to be
controlled by a single coil.
*Note:
It is possible to leave the Fail and/or Enable
Coil fields off if the coils are not going to be
used. However, it is recommended that a
value of zero be used to explicitly indicate this.
Refer to Configuration Figure 6 below for two
examples of complete scheduler entries.
#name port
interval
slave
address
function
slave
start
count
master
start
fail
coil
en.
coil
#
#
T1,
1,
1000, 1, 3, 3001, 10,
3010,
3001, 3011
# Interface Module port 1 in MODBUS Master mode, querying the slave with address
# 1 every 1,000 milliseconds for 10 holding register, starting at slave holding
# register 3001 and storing the value in the interface module starting at
# holding register 3010. Coil 3011 enables the transfer, errors are reported
# to 3001
Comments begin
with "#" symbol
Scheduler
entries
containing
eight required
(and two
optional) fields
# Interface Module port 1 in MODBUS Master mode, writing to the slave with address 4 every
# 500 milliseconds for 1 coil. Value is read from Interface Module register 3001, and written
# to slave register 3001. Coil 3111 enables the transfer, errors are reported
# to 3101
Example 1:
Example 2:
#name port
interval
slave
address
function
slave
start
count
master
start
fail
coil
en.
coil
#
#
T2, 1, 500, 4, 6, 3001, 1, 3001, 3101, 3111
Configuration Figure 6.
Example of Scheduler Entries