Safe Mode Jumper
When installed, the Safe Mode Jumper causes the
following changes to the boot up sequence:
- All user accounts and passwords are deleted
and reset to factory defaults
- If configured for MODBUS RTU Master mode,
the master is not started and no queries are
issued
- The ISaGRAF Control Engine is not started. No
program logic is executed.
Removing the jumper and rebooting will cause the
NCS to boot normally.
Safe Mode Jumper Installation:
1.
Power down the Interface Module by removing the
power cables from it.
2. Remove the left side panel from the Interface
Module by removing the six side panel screws.
3.
Place the Safe Mode Jumper on both pins as
illustrated in Configuration Figure 8 under the Safe
Mode (
Passwords Reset)
illustration, and power
up the Interface Module.
4.
Power down the Interface Module and remove
the safe mode jumper, placing it back on the
jumper as shown in the
Normal Mode
illustration.
Replace the side panel, and power up the module.
It is now ready for use.
5.
Start the Web Server, and use the administrative
account with a username of
root
and a password
of
password
, to access the system and make any
necessary changes. A guest account with the
username of
guest
and a password of
password
is
also available for use.