NET Concentrator System
®
NCS
- 96 -
Moore Industries-International, Inc.
www.miinet.com
BIT
Position Description
Troubleshooting
1
Bad Transfer Definition (there are one
or more mistakes in schedule.ini).
The schedule.ini file contains one or more
syntax error. Check the "Status Details" to
determine which line the error is on.
0
System Fault.
System Error.
3
Exception Response (one or more
transfers returned a MODBUS
exception code).
A non-supported function code was used
An out of range register/coil was requested
Too many registers were requested
2
Timeout (one or more transfers were
not responded to).
The Response Timeout Setting is too short for
the combination of baud rate, query/response
length, and slave response time;
There is a network problem Check baud rates,
and the address assigned to the slave;
Instead of returning an Exception Response
to improper queries, some slaves simply do
not respond.
Use the "Status Detail"
button on the
MODBUS
web page to
determine
which slave is
returning
the Exception
Response.
BIT
Position Description
Troubleshooting
2
The file system is full
Too many configurations, custom curves, or
large ISaGRAF resources are in the filesystem.
Use FTP to delete the contents of the cfg and
hds folders.
0
File system initialization error. Indicates
that the state of the file system cannot
be determined. Depending on the type
of error, the NCS may attempt to
automatically format the file system.
1
New file system. Indicates that the file
system has been formatted. Normally,
this is only performed once at the initial
system startup. However, an automatic
format can occur if the file system
becomes corrupted.
Cycle power, and contact Customer Support
if the condition does not clear itself.
BIT
Position Description
Troubleshooting
5
Custom engineering units (EGU) file
not found
Configure any channel to create the EGU file
3
Detected module types do not match
those which are expected
On the System Status web page, click
the "Accept Module Types" button.
1
Missing or corrupted password file or
password jumper was detected.
Default password file loaded.
Cycle power to clear the error
4
Channel tag file not found
Configure any channel to create the tags file.
2
File containing expected module types
was not found
0
Missing system configuration file
Use NAC Client to reconfigure network
settings, and then reconfigure MODBUS.
BIT
Position Description
Troubleshooting
1
Data Logger failed to restore records
from non-volatile RAM
There was a problem with non volatile storage.
Check the "Clock Battery Fail" bit in the System
Time Substatus register
0
Data Logger could not be initialized
The logger configuration file is either missing
or was corrupted. Click Update on the Configure
Data Logger web page
Appendix Table 10.
MODBUS Master Status Register Bit Positions
Appendix Table 11.
File System Status Register Bit Positions
Appendix Table 12.
Configuration Status Register Bit Positions
Appendix Table 13.
Data Logger Status Register Bit Positions