NET Concentrator System
®
NCS
- 76 -
Moore Industries-International, Inc.
www.miinet.com
Mechanical Output Ratings:
SPST relay, 1 form A or B,
rated 2A@250Vac, 50/60Hz
or 2A@30Vdc, non-inductive
Output Logic:
Logic 1 yields
energized relay
Output Failure Mode:
Outputs are programmable
to either hold last value, or
go energized or de-energized
upon lost communication with
the Interface Module
Scan Time:
16ms
Isolation:
500Vrms,
continuous, from channel to
channel, from each channel to
case, and from each channel
to terminals of other attached
NCS modules; will withstand
1000Vrms dielectric strength
Performance
LED
Indicators
test for one minute, with
no breakdown, from each
channel to case, and from
each channel to terminals of
other attached NCS interface
modules
Response Time:
<10ms
Power Supply:
Power is
supplied by the Interface
Module, 3W maximum
Diagnostic Information:
Refer to Appendix B Table 9
Performance
(continued)
Ambient
Conditions
One red/green LED per
channel indicates relay state
and can be programmed for
desired sense
Operating Range:
–40°C to +85°C
(–40°F to +185°F)
Storage Range:
–40°C to +85°C
(–40°F to +185°F)
Relative Humidity:
0-95%, non-condensing
RFI/EMI Protection:
20V/m
@20-1000MHz, 1kHz AM
when tested according to
IEC1000-4-3-1995
493 g (17.4 oz)
Weight
ROM Module Figure 1. ROM Dimensions
Specifications
75mm
(2.96 in)
135mm
(5.34 in)
118mm
(4.66 in)
ROM FRONT
LEFT SIDE
RIGHT SIDE
Module
Number
ROM8
RELAY OUTPUT MODULE
87mm
(3.45in)
CHANNEL 1
CHANNEL 2
CHANNEL 3
CHANNEL 4
CHANNEL 5
CHANNEL 6
CHANNEL 7
CHANNEL 8
The ROM Relay
Output Module
The Relay Output Module (ROM) accepts information
from the NCS Interface Module and outputs it to
eight independently configurable relay signals. Each
relay can be configured as normally open or normally
closed by jumper selection. The power and failure
states and led indications are software programmable.
All Channels:
Power Up State: Off
Output On Fail: Hold
LED’s When Energized: Red
Default Configuration
Note:
Earlier Models have a
different DIN latch but
overall dimensions are the
same and both versions
are interchangeable.