NET Concentrator System
®
NCS
- 54 -
Moore Industries-International, Inc.
www.miinet.com
CHANNEL 1
CHANNEL 2
CHANNEL 3
CHANNEL 4
Module
Number
75mm
(2.96 in)
135mm
(5.34 in)
118mm
(4.66 in)
AIM FRONT
LEFT SIDE
RIGHT SIDE
AIM
ANALOG INPUT MODULE
91mm
(3.6 in)
AIM Module Figure 1.
AIM Dimensions
Specifications
Specifications and information subject to change without notice.
Performance
Performance
(continued)
Status
and
Fault
Indicators
Ambient
Conditions
Weight
Input Ranges:
Programmable for any range
within: Current, 0-25mA
(4mA minimum span) or
Voltage, -10V to +10V
(1V minimum span)
Accuracy:
±0.01% of
maximum span
Input Resolution:
20-bit
Stability (% of maximum
span):
Current:
1-year, 0.047%;
3-year, 0.081%;
5-year, 0.11%
Voltage:
1-year, 0.066%;
3-year, 0.11%;
5-year, 0.15%
Isolation:
500Vrms,
continuous, from channel to
channel, from each channel
to case, and from each
channel to terminals of other
attached
NCS
modules;
will withstand 1000Vrms
dielectric strength test for one
minute (with no breakdown)
from each channel to case,
and from each channel to
terminals of other attached
NCS
modules
Scan Time:
The time
required for the
NCS
Module
to access process variable
and status data from all four
channels of the AIM is 16ms
Response Time:
60ms
Input Impedance:
Current, 20 ohms;
Voltage, 1 Mohm
Maximum Input Overrange:
Current, ±100mA; Voltage,
±30V
Power Supply:
Power is
supplied by the
NCS
Module,
4W maximum
Input Filter:
User-Programmable for 50Hz
or 60Hz noise rejection
Linearization Capability:
Custom curve tables can be
configured with up to 128
points using Internet Explorer
web pages or
PC-based software
Transmitter Excitation:
21V/24mA excitation for
powering a 2-wire transmitter
Diagnostic Information:
Refer to Table 14
One red/green LED per
channel indicates proper
channel operation (green) or
that the channel is in a fault
condition (red)
Operating Range:
-40°C to +85°C
(-40°F to +185°F)
Storage Range:
-40°C to +85°C
(-40°F to +185°F)
Ambient Temperature
Effect:
0.01% of maximum
span/°C
Relative Humidity:
0-95%, non-condensing
RFI/EMI Protection:
20V/m
@20-1000MHz, 1kHz AM
when tested according to
ENC61000-4-3-1996
Common Mode Rejection:
100dB@50/60Hz
Normal Mode
Rejection:
Current, 60dB
typical@10mAp-p; Voltage,
60dB typical@1Vp-p,
50/60Hz
562 g (19.8 oz)
The AIM Analog Input Module
The Analog Input Module (AIM) isolates and
conditions four analog signals and relays input
information to the NCS Interface Module.
All Channels:
4-20mA Filter 60Hz
Input Scaling:
Disabled
Trimming:
Disabled
Custom Curve:
Disabled
Default Configuration
Note:
Earlier Models
have a different
DIN latch but
overall dimensions
are the same and
both versions are
interchangeable.