NET Concentrator System
®
NCS
- 89 -
Moore Industries-International, Inc.
www.miinet.com
CE Conformity
Installation of Moore Industries’ Net Concentrator
System product which bares the CE mark must
adhere to the guidelines in the Installation section
in order to meet the requirements set forth in the
applicable European Union EMC (Electromagnetic
Compatibility) Directive and the LVD (Low Voltage
Directive).
Maintenance
Moore Industries suggests a quick check for terminal
tightness and general unit condition every 6-8
months. Always adhere to any site requirements for
programmed maintenance.
Adding new I/O Modules
Interface Modules are now aware of the I/O modules
which are expected to be present. When any I/O
module is added or changed in the system, the user
must use the System Status page in the web server to
click the “Accept Module Types” button. Clicking on
this button tells the interface module that the currently
attached module types are correct. If the system is
rebooted, and a different module type or module count
is detected, a bit will be set in the Configuration Status
Register..
Installations in Hazardous
Locations
This section contains important information regarding
installation of the NCS in hazardous area locations.
WARNING:
To prevent ignition of flammable or combustible
atmospheres, disconnect power before servicing.
AVERTISSEMENT:
Risque d’explosion. Avant de déconnecter
l’equipement, couper le courant ou s’assurer que
débrancher tant que l’emplacement est désigné non
dangereux.
WARNING:
Explosion Hazard. Substitution of components may
impair suitability for Class I, Division 2
AVERTISSEMENT:
Risque d’explosion. La substitution de composants
peut rende ce materiel inacceptable pour les
emplacements de Classe I, Division 2.
Speci
fic
Conditions of Use
The following instructions must be adhered to when
the NCS NET Concentrator System is used in
hazardous locations.
cFMus Installations
Nonincendive applications
Class I Division 2 Groups A-D
The model NCS NET Concentrator System shall be
shall be installed in a final enclosure meeting the
requirements of ANSI/ISA 61010-1 and the National
Electrical Code, or C22.2 No. 1010.1 and the Cana
-
dian Electrical Code.
The model NCS NET Concentrator System shall be
installed in compliance with the enclosure, mounting,
spacing and segregation requirements of the ultimate
application.
Connections shall not be made to the communications
“COM” port, “Ethernet”, and or “USB” port in Hazard
-
ous Locations.
Customer Support
Moore Industries is recognized as the industry leader
in delivering top quality to its customers in products
and services. We perform a battery of stringent qual-
ity assurance checks on every unit we ship. If any
Moore Industries product fails to perform up to rated
specifications, call us for help. Our highly skilled staff
of trained technicians and engineers pride themselves
on their ability to provide timely, accurate, and practical
answers to your process instrumentation questions.
Factory phone numbers are listed on the back cover
of this manual.
If problems involve a particular NCS Module, there
are several pieces of information that can be gathered
before you call the factory that will help our staff get
the answers you need in the shortest time possible.
For fastest service, gather the complete model and
serial number(s) of the problem unit(s) and the job
number of the original sale.
Содержание NET Concentrator System AOM
Страница 33: ...NET Concentrator System NCS 33 Moore Industries International Inc www miinet com NCS as MODBUS Slave...
Страница 36: ...NET Concentrator System NCS 36 Moore Industries International Inc www miinet com NCS as MODBUS Master...
Страница 92: ...NET Concentrator System NCS 92 Moore Industries International Inc www miinet com Appendix B MODBUS Registers...