NET Concentrator System
®
NCS
- 78 -
Moore Industries-International, Inc.
www.miinet.com
Failure Response-
This section tells the ROM what
to do if communication with the Interface Module fails.
It will either maintain the last value (
Hold
), or turn the
relay to a predetermined energized or de-energized
state (
On/Off
).
Output Test-
This function allows you to change
the state of each relay. After clicking
Output Test
,
use the check boxes to select the desired relay and
press
Update Output
. A checked box energizes the
corresponding relay.
Commit/Cancel Buttons-
Click
Commit
when you
are finished selecting parameters to save the settings
to memory.
Cancel
ends your configuration without
saving changes.
Configuring the ROM
The ROM can be configured using the web server
contained within the Interface Module to which it is
attached. It can also be configured using the NCS PC
Configuration Software. For further details please see
the
Navigating the PC Program
in the
Configuration
Section
of this manual. To configure the ROM,
you must first mount it to the Interface Module as
described in
Installing the I/O Modules
.
To access real-time data using MODBUS commands
instead of the web server, see
the MODBUS/TCP
Support
section in the MODBUS chapter of this
manual.
Note:
The ROM I/O module is set to factory defaults,
to use either method mentioned above to
configure with your desired parameters
.
When energized, LEDs are-
This setting allows user
to choose color (red or green) of the LED when the
relay is energized.
Saving Configuration Settings-
If you will be using
a common configuration within your system, you can
create a configuration and save it to a file so that
you can load it into another I/O module. Refer to the
Saving Configuration Settings
section of this manual
for more information
Tag-
Assign a tag name, or descriptor, to process
variables for each channel. The
Process Status
page
will display the data next to the respective process
variable tag. These tags can also be read by the OPC
Server and can therefore be used to access process
data in the
NCS when configuring an OPC client.
Relay on Powerup-
Checking a box configures the
corresponding relay to be on (energized) upon power
up for each channel for which you have checked the
box.