NET Concentrator System
®
NCS
- 70 -
Moore Industries-International, Inc.
www.miinet.com
The AOM Analog Output
Module
The Analog Output Module (AOM) accepts
information from the NCS and outputs it as one of four
independently configurable analog signals.
Specifications and information subject to change without notice.
Performance
(continued)
Performance
(continued)
Status
and Fault
Indicators
Ambient
Conditions
Weight
Performance
Output Ranges:
Programmable for any range
within: Current (sink or
source), 0-20mA or Voltage,
0-10V
Accuracy:
±0.015% of
maximum span
Output Resolution:
18-bit
Stability (% of max. span):
Current:
1-year, 0.012%;
3-year, 0.020%;
5-year, 0.026%
Voltage:
1-year, 0.066%;
3-year, 0.11%;
5-year, 0.15%
Isolation:
500Vrms,
continuous, from channel to
channel, from each channel
to case, and from each
channel to terminals of other
attached NCS modules; will
withstand 1000Vrms dielectric
strength test for one minute,
with no breakdown, from each
channel to case, and from
each channel to terminals of
other attached NCS modules
Scan Time:
The time
required for the Interface
Module to access process
variable and status data from
all four channels of the AOM
is 16ms
Response Time:
50ms to 90% of final value
on a step input
Output Damping:
Increases response
time by adjusting filter
time constant from 0-30
seconds
Ripple:
Current, 10mV
peak-to-peak measured
across a 250ohm load
resistor; Voltage, 50mV
peak-to-peak maximum
Load Capability:
Current, 0-1000ohms
(source), 42V maximum
(sink) 1500ohms; Voltage,
0-5mA (2000 ohms
minimum load)
Output Limiting:
Current
output is guaranteed
up to 21.6mA (or 10%
of full scale above the
programmed full value)
and limits at 23.6mA;
Voltage output accuracy
is guaranteed up to 10.5V
(or 5% of full scale above
the programmed full
value) and limits at 11.0V
Load Effect (current
outputs):
0.01% of span
from 0 to maximum load
resistance on current
output
Output Failure Mode:
Outputs are programmable to
either hold last value or go to
a pre-defined value on error
upon lost communication
with the Interface Module or
upon receiving invalid primary
variable data
Power Supply:
Power is supplied by the
Interface Module,
4W maximum
Diagnostic Information:
Refer to Appendix B Table 8
One red/green LED per
channel indicates proper
channel operation (green) or
that the channel is in a fault
condition (red)
Operating Range:
–40°C to +85°C
(–40°F to +185°F)
Storage Range:
–40°C to +85°C
(–40°F to +185°F)
Ambient Temperature
Effect:
0.01% of maximum
span/°C
Relative Humidity:
0-95%, non-condensing
RFI/EMI Protection:
20V/m@20-1000MHz, 1kHz
AM when tested according to
ENC61000-4-3-1996
765 g (27 oz)
Specifications
All Channels:
0-20mA
Under Range: 0mA
Over Range: 23.6mA
Output On Failure: Hold Last
Trimming: Disabled
Default Configuration