EtherNet/IP™ CIP Safety™ IP67 HarshIO 600
111
IP67 Safety Digital I/O Modules
Select the
Module Configuration
tab to define the parameters for the Safety Inputs and Safety Outputs.
Safety Inputs Configuration
1. Point Operation Type
Type
Comments
Single
Safety Inputs are treated separately.
Equivalent
Safety Inputs are treated as an
Equivalent dual-channel
. The
evaluation is done after discrepancy time.
Complementary
Safety Inputs are treated as a
Complementary dual-channel
. The
evaluation is done after discrepancy time.
2. Point Mode
Mode
Comments
Not used
Input is disabled.
Safety
Input is enabled and no external pulse test is needed. This is
commonly used when the Input device generates its own pulse test
such as light curtain.
Safety Pulse
Test
Input is enabled and a Pulse Test must be used as the 24 V. The pulse
test is configured via the
Test Source
option.
Standard
Input is enabled but
doesn’t participate in any safety function. This is
commonly used to connect non-safe input device.
1
2
3
4
5
6