EtherNet/IP™ CIP Safety™ IP67 HarshIO 600
113
IP67 Safety Digital I/O Modules
Safety Outputs Configuration
1. Point Operation Type
Mode
Comments
Single
The Safety Outputs are treated separately.
Dual Channel
The Safety Outputs are treated as a dual-channel.
2. Point mode
Mode
Comments
Not used
Output is disabled.
Safety No Pulse Test
Output is enabled and NO pulse test is generated.
Safety Pulse Test
Output is enabled and a pulse test is generated.
3. Pulse Test Length
Define the pulse test length of the associated Output. See
Output Pulse Test
for more information.
1
2
3
4
Содержание TCDEC-8B4B-D1U-G8
Страница 141: ...EtherNet IP CIP Safety IP67 HarshIO 600 141 IP67 Safety Digital I O Modules Select Yes Select Yes ...
Страница 166: ...EtherNet IP CIP Safety IP67 HarshIO 600 166 IP67 Safety Digital I O Modules ...
Страница 181: ...EtherNet IP CIP Safety IP67 HarshIO 600 181 IP67 Safety Digital I O Modules 14 Certifications ...
Страница 182: ...EtherNet IP CIP Safety IP67 HarshIO 600 182 IP67 Safety Digital I O Modules TUV Certificate ...