EtherNet/IP™ CIP Safety™ IP67 HarshIO 600
136
IP67 Safety Digital I/O Modules
Safety Reset
The Safety Reset is a command to reset the ownership between the EtherNet/IP Scanner and a HarshIO
module in case of one of the below parameter has changed:
• HarshIO TCP/IP address
• HarshIO Safety Network Number (SNN)
• HarshIO configuration signature
Note!
The command is useful if a HarshIO module already commissioned needs to be reset
with the factory “out-of-box” configuration setting (meaning default SNN, no
configuration signature and no stored IP address).
Note!
The procedure is based on the assumption that the module has been already
commissioned and no information is known about the module (IP address, SNN, lock,
signature, password…).
To perform a Safety Reset follows the below procedure:
1.
Set the computer network interface to
192.168.1.100
.
2.
Open the HarshIO module window and set the 3 rotary switches to position
001
(corresponding to static
IP address
192.168.0.1
)
3.
Power up the module
4.
Launch the SNCT
5.
Create a new project (
File/New
)
6.
Select the correct safety module model and version
Содержание TCDEC-8B4B-D1U-G8
Страница 141: ...EtherNet IP CIP Safety IP67 HarshIO 600 141 IP67 Safety Digital I O Modules Select Yes Select Yes ...
Страница 166: ...EtherNet IP CIP Safety IP67 HarshIO 600 166 IP67 Safety Digital I O Modules ...
Страница 181: ...EtherNet IP CIP Safety IP67 HarshIO 600 181 IP67 Safety Digital I O Modules 14 Certifications ...
Страница 182: ...EtherNet IP CIP Safety IP67 HarshIO 600 182 IP67 Safety Digital I O Modules TUV Certificate ...