1) Request message processing time [unit: ms]
Tsl = Ttq + Ta + Ks1 + Ks2 n1 + (Sm + LS 4 + T
RIOR
+ T
RBF
) n2 + Ttr +Ti 2
+ Gt
2) Calculation items
* 1 Refer to the Q Corresponding MELSECNET/H Network System Reference Manual (Remote I/O
network).
TableApp.11 Processing time calculation time used when mounted on a MELSECNET/H remote I/O station
Item
Description
Unit
Sm
Remote master station scan time
ms
LS
Link scan time
*1
ms
T
RIOR
I/O refresh time
*1
ms
T
RBF
Time of refresh with buffer memory of intelligent
function module
*1
ms
Other than the above
Refer to(2) (a) in this appendix.
-