4
- 55
4.17 Read File Record (FC: 20) (SC: 06)
4
MODBUS(R) STANDARD FUNCTIONS
4.17 Read File Record (FC: 20) (SC: 06)
Reads multiple extended file register values.
(1) Request message format (Master Slave)
* 1 The maximum file number available for the QJ71MB91 slave function is dependant on the file
register size of the mounted programmable controller CPU.(
(a) Number of sub-requests, m
Specify the number of sub-requests, m, so that the protocol data unit size of the
request message will not exceed 253 bytes.
*2
2 + m
7
253
*2
If the above condition is not satisfied, the request message is discarded.
* 2 When the frame mode is ASCII mode, it is 506 bytes.
(b) Read points of each sub-request
Specify the total points N (n1+...+nm) so that the protocol data unit size of the
response message will not exceed 253 bytes.
*3
2 + m
2 + N
2
253
*3
If the above condition is not satisfied, the slave returns an exception response.
* 3 When the frame mode is ASCII mode, it is 506 bytes.
Figure 4.91 Read file record (Request message)
Data
(L)
(L)
(L)
Sub-request
1
Data
(L)
(L)
(L)
Function code
Function
code
(14
H
)
Number of
bytes
m x 7
Reference
number
(06
H
)
File number
(0000
H
to FFFF
H
) *
1
Read head device number
(0000
H
to 270F
H
)
Read points
n1
(0001
H
to 007C
H
)
(Number of bytes m x 7)
(Number of bytes m x 7)
Sub-request m
Reference
number
(06
H
)
File number
(0000
H
to FFFF
H
) *
1
Read head device number
(0000
H
to 270F
H
)
Read points
nm
(0001
H
to 007C
H
)
(H)
(H)
(H)
(H)
(H)
(H)
Содержание QJ71MB91
Страница 1: ......
Страница 2: ......
Страница 366: ...App 14 Appendix 4 External Dimensions APPENDICES Memo ...
Страница 371: ......
Страница 372: ......