(5) Type specification of the target MODBUS device
Specify the types of the read/write target MODBUS devices.
(a) Setting range
Available combinations of the read and write targets are as shown in the table
below.
No other combinations are available.
* 1 To perform only read or write, set "0" to each of the following:
Head buffer memory address (
Target MODBUS
device head number (
Access points (
* 2 Reading and writing can be performed simultaneously with one instruction only when 0505
H
(Read/write multiple registers) is set.
* 3 Broadcast can be performed with 0001
H
(Write multiple coils) and 0005
H
(Write multiple registers)
only.
Figure 7.5 Structure for Type specification of the target MODBUS
device
Table7.2 Type specification of the target MODBUS
device
Setting value
Target MODBUS
device type
00
H
No specification
01
H
Coil
02
H
Input
04
H
Input register
05
H
Holding register
Table7.3 Setting range for Type specification of the target MODBUS
device
Type specification of the target MODBUS
device
Function code
Setting
value
Read target
Write target
0100
H
Coil
No specification
*1
01 Read coils
0200
H
Input
02 Read discrete inputs
0400
H
Input register
04 Read input registers
0500
H
Holding register
03 Read holding registers
0001
H
No specification
*1
Coil
*3
15 Write multiple coils
0005
H
Holding register
*3
16 Write multiple registers
0505
H
Holding register
*2
Holding register
23 Read/write multiple registers
b15
b8 b7
b0
Read target
Write target