11
- 43
11.5 Turning Off the ERR. LED
11.5.1 Turning off the ERR. LED by GX Configurator-MB
11
TROUBLESHOOTING
(a) LEDs that will be cleared
When error clear requests are made by "CH Common/CH1 Error clear request"
and "CH2 Error clear request" on the Monitor/test screen (
Section 8.6), all
the LEDs and the Exception code storage area (0002
H
/0004
H
) in the buffer
memory are cleared.
*1
* 1 For the execution of "Y1B: CH common/CH1 error clear request" and "Y1C: CH2 error clear
request" on the X/Y monitor/test screen (
Section 8.6.1), only the LED, whose clear is
requested in the Detailed LED clear request storage area (address: 0008
H
/0009
H
) in the buffer
memory, is cleared.
When the LED was turned off by "Y1B: CH common/CH1 error clear request" and "Y1C: CH2 error
clear request", turn on the corresponding bit in the Detailed LED clear request storage area by the
device test on GX Developer.
Figure 11.10 Configuration of the Detailed LED clear request storage area
b0
b1
b2
b3
b4
b5
b6
b7
b8
b9
b10
b11
b12
b13
b14
b15
1/0 1/0 1/0 1/0 1/0
b0
b1
b2
b3
b4
b5
b6
b7
b8
b9
b10
b11
b12
b13
b14
b15
1/0 1/0 1/0 1/0 1/0
1/0
1/0
CH1 side Detailed LED clear request storage area (address: 0008
H
)
CH2 side Detailed LED clear request storage area (address: 0009
H
)
Unused (Fixed to 0)
Unused (Fixed to 0)
CH1 error response code
storage area (0002
H
)
CH2 error response code
storage area (0004
H
)
0: Not cleared
1: Clear request
0: Not cleared
1: Clear request
CH1 C/N
CH1 P/S
CH1 PRO.
CH1 SIO
C/1 ERR.
CH2 C/N
CH2 P/S
CH2 PRO.
CH2 SIO
CH2 ERR.
Содержание QJ71MB91
Страница 1: ......
Страница 2: ......
Страница 366: ...App 14 Appendix 4 External Dimensions APPENDICES Memo ...
Страница 371: ......
Страница 372: ......