6
- 21
6.6 Intelligent Function Module Switch Setting
6
PRE-OPERATIONAL PROCEDURES AND SETTINGS
(a) Mode setting (Switch 1: CH1 side, Switch 3: CH2 side)
Set the operation mode of the QJ71MB91.
* 1 Setting a value other than indicated in the table results in a switch error.
* 2 For the link operation (slave function), set "0002
H
" to both Switch 1 and 3.
Setting it to only one switch results in a switch error.
Table6.7 Mode setting
Set value
*1
Operation mode
Description
Switch 1
Switch 3
CH1
CH2
0000
H
0000
H
Master function
Master function
Master function : Performs communication as master
station.
Slave function : Performs communication as slave
station.
0000
H
0001
H
Master function
Slave function
0001
H
0000
H
Slave function
Master function
0001
H
0001
H
Slave function
Slave function
0002
H
0002
H
Link operation (Slave function)
*2
Relays data between CH1 and CH2 with the link operation
function. (
000D
H
000D
H
Hardware test
Performs test to check the RAM and ROM of
QJ71MB91.(
000E
H
000D
H
Self-loopback test
-
Performs tests to check the send/receive function of the
QJ71MB91 and communications with the programmable
controller CPU.
(
000D
H
000E
H
-
Self-loopback test
000E
H
000E
H
Self-loopback test
Self-loopback test