8.4 Initial Setting
8.4.1 Automatic communication parameter
8
UTILITY PACKAGE (GX Configurator-MB)
[Setting items]
For the automatic communication parameter setting, set a value in proper data format
or within the setting range for each item in the Setting value column, and click the
button to save all the set values.
POINT
After the automatic communication parameters have been written to the
programmable controller CPU, the automatic communication function is operated
when the programmable controller is powered ON from OFF or the programmable
controller CPU is reset (with the programmable controller CPU’s RUN/STOP
switch set to RUN).
Table8.7 Setting items on Automatic communication parameter setting screen
Setting item
Buffer memory address
Reference
CH1
CH2
Automatic
communication
parameter 1
Setting parameter existence
0200
H
to
0201
H
(512 to 513)
0380
H
to
0381
H
(896 to 897)
Target station No.
0202
H
(514)
0382
H
(898)
Request interval timer value
0203
H
(515)
0383
H
(899)
Response monitoring timer value/Broadcast delay value
0204
H
(516)
0384
H
(900)
Type specification of the target MODBUS(R) device
0205
H
(517)
0385
H
(901)
Read setting
Head buffer memory address
0206
H
(518)
0386
H
(902)
Target MODBUS(R) device head number
0207
H
(519)
0387
H
(903)
Access points
0208
H
(520)
0388
H
(904)
Write setting
Head buffer memory address
0209
H
(521)
0389
H
(905)
Target MODBUS(R) device head number
020A
H
(522)
038A
H
(906)
Access points
020B
H
(523)
038B
H
(907)
Automatic
communication
parameter 2 to
32
(Same as in automatic communication parameter 1)
020C
H
to
037F
H
(524 to 895)
038C
H
to
04FF
H
(908 to
1279)
End setup