11
- 31
11.4 Error Codes
11.4.3 Error code list
11
TROUBLESHOOTING
Table11.16 Error code list (Continued)
Error Code
Error Name
Description
Corrective Action
Occurrence
1)
2)
3)
4)
5)
730A
H
(29450)
Parameter starting
method error
Parameter setting using GX
Configurator-MB was applied to the
programmable controller CPU while the
MODBUS
device assignment
parameter starting method specified by
the intelligent function module switch
was set to "Start with the default
parameters".
• When using the default parameter
setting, delete the QJ71MB91
parameters entered to the
programmable controller CPU.
• When starting the QJ71MB91 with
parameters set from GX
Configurator-MB or the sequence
program, turn ON the MODBUS
device assignment parameter
starting method of the intelligent
function module switch.
7327
H
(29479)
CPU response
monitoring timer
setting error
The CPU response monitoring timer
value in the buffer memory (address:
000D
H
) is incorrect.
Review the CPU response monitoring
timer value.
7330
H
(29488)
Device code error
The device code value specified as a
MODBUS
device assignment
parameter is incorrect.
Review the device code value.
7331
H
(29489)
MODBUS
device
upper limit value
over error
The head MODBUS
device number
+ assigned points in the MODBUS
device assignment parameter exceeds
the maximum value (65535) allowed for
the MODBUS
device.
Review the head MODBUS
device
number and the number of assigned
points.
7332
H
(29490)
MODBUS
device
assigned range
overlap error
MODBUS
device ranges set with
the MODBUS
device assignment
parameters are overlapped.
Review the head MODBUS
device
number and the number of assigned
points.
7333
H
(29491)
Buffer memory
assigned range error
The assigned range of the QJ71MB91
buffer memory set with the
MODBUS
device assignment
parameter exceeds the range of the
user free area.
Review the head device number and
the number of assigned points.
7334
H
(29492)
Device upper limit
value over error
The head device assigned
points in the MODBUS
device
assignment parameter exceeds the
maximum value (65535) allowed for the
CPU device.
Review the head device number and
the number of assigned points.
7335
H
(29493)
Error status read
device setting error
The specification of the error status
read device is incorrect.
Review the setting of the error status
read device.
7336
H
(29494)
MELSECNET/H
remote access target
value error
The access target specification value is
other than 0 and 1 when the
QJ71MB91 is mounted on the
MELSECNET/H remote I/O station.
Set the access target specification
value to 0 or 1 when the QJ71MB91 is
mounted on the MELSECNET/H
remote I/O station.
7337
H
(29495)
MELSECNET/H
remote access target
error
The access target (when mounted to
MELSECNET/H remote I/O station)
(address: 000E
H
) was set when the
QJ71MB91 is not mounted on the
MELSECNET/H remote I/O station.
Review the access target station or the
specified access target value (when
mounted to MELSECNET/H remote I/O
station).
7338
H
(29496)
Buffer memory
setting error
Data were written to the system area
(use prohibited) in the buffer memory.
Check whether or not writing to the
system area (use prohibited) in the
buffer memory was executed by the
sequence program.
R