- 5
10.2 Z(P).MBRW
10
DEDICATED INSTRUCTIONS
Table10.5 Control data of the MBRW instruction (Continued)
Device
Item
Setting data
Setting range
Setting
side
*1
(S1)+9
Read
set
ting
Target file
number
Specify a file number when the target MODBUS
device is the extended file
register.
0 to 65535
*2*3
User
(S1)+10
Target
MODBUS
device head
number
Specify the head number of the read target MODBUS
device.
Specify the lower 5 digits of the device head number.
The device head number is specified as "(Actual device number) - 1".
(Except for the file number and device number of the extended file register)
(Example) Specify "31" when accessing Input 100032.
0 to 65535
*2*3
User
(S1)+11
Access
points
Set the read points of the MODBUS
device.
The units used for the setting of access points are as follows:
0 to 2000
*3
User
Target MODBUS
device type
specification
Unit
Allowable access points
01
H
: Coil
02
H
: Input
Bit
04
H
: Input register
05
H
: Holding register
07
H
: Extended file register
Word
(S1)+12
Read data
storage size
Set the word size of the read data stored in the argument (D1) and later fields.
-
System
(S1)+13
W
rite settin
g
Target file
number
Specify a file number when the target MODBUS
device is the extended file
register.
0 to 65535
*2*4
User
(S1)+14
Target
MODBUS
device head
number
Specify the head number of the write target MODBUS
device.
Specify the lower 5 digits of the device head number.
The device head number is specified as "(Actual device number) - 1".
(Except for the file number and device number of the extended file register)
(Example) Specify "31" when accessing Holding register 400032.
0 to 65535
*2*4
User
(S1)+15
Access
points
Set the write points of the MODBUS
device.
The units used for the setting of access points are as follows:
0 to 1968
*4
User
Target MODBUS
device type
specification
Unit
Allowable access points
01
H
: Coil
02
H
: Input
Bit
04
H
: Input register
05
H
: Holding register
07
H
: Extended file register
Word
(S1)+16
Write data
storage size
Set the word size of the write data stored in the argument (S2) and later fields.
Set "1" for the case of read only.
When the access target MODBUS
device (Type specification of the target
MODBUS
device) is "01
H
: Coil" or "02
H
: Input", pay attention to the following.
• Set the "Number of access points/16 (rounded up to the nearest integer)" as the
write data storage size.
• When the number of write points is a number with a fraction, the excess area is
ignored. (Refer to Point.)
1 to 125
User