11
TROUBLESHOOTING
11.4 Error Codes
11.4.3 Error code list
11
- 40
9
P
R
OGRAM
M
ING
10
D
E
DICA
TED
INSTRUC
TI
ONS
11
TR
O
U
BLE
S
HOOTING
A
P
P
E
NDICE
S
INDE
X
Table11.16 Error code list (Continued)
Remark
1. For details of areas to which error codes are stored, refer to Section 11.4.1
2. For details of parameter setting ranges and other information, refer to
CHAPTER 7
Error code
Error Name
Description
Corrective Action
Occurrence
1)
2)
3)
4)
5)
7411
H
(29713)
CRC/LRC error
The CRC/LRC in the received
message does not match the CRC/
LRC calculated by the QJ71MB91.
• Do not turn OFF or disconnect the
device from the network while it is
sending a message. (If this is the
cause of t he error, no action is
required as long as there is no
particular problem.)
• Review the contents of the message
issued by the relevant station.
• Check the relevant device.
• Disconnect the erroneous device if
any.
• Review the line status.
• Take preventive measures against
noise.
7412
H
(29714)
Transmission
monitoring timer
timeout
The transmission monitoring timer
timed out.
• Confirm that the cables are not
disconnected.
• Check the cable connection and
correct the wiring so that the CS
signal on the CH1 (RS-232) side will
be always ON.
7480
H
to 75FF
H
(29824 to
30207)
System error
The OS of the QJ71MB91 detected a
fault.
Take the following steps:
• Check if the power supply module,
programmable controller CPU and
QJ71MB91 are correctly mounted on
the base unit.
• Confirm that the system is operated
within the general specifications of
the programmable controller CPU.
• Check if the power capacity is
sufficient.
• A probable cause is a hardware
error.
Check if the programmable controller
CPU, base unit and QJ71MB91 are
normal referring to the manual for
each module.
Or, replace any of the modules to
check the operation.
• If the above does not solve the
problem, please consult your local
Mitsubishi system service center or
representative, explaining a detailed
description of the error occurrence,
the GX Developer project and/or the
error code.
F000
H
to
FFFF
H
(61440 to
65535)
-
Errors detected by MELSECNET/H or
MELSECNET/10 network module
Refer to the troubleshooting section in
the MELSECNET/H or MELSECNET/
10 Network System Reference Manual,
and take the corrective actions.