2 - 33 2 - 33
MELSEC-Q
2 USING THE E-MAIL FUNCTION
News settings
Notification condition
Item name
Description of setting
CPU status
monitoring (
1)
Device
monitoring
Setting range/option
Condition for PLC
inspection
Select the monitoring condition for the
CPU
• No setting
• Normal STOP
• Module error/Module system error
(Serious/Fatal Error)
• Module warning STOP
(Moderate error STOP)
• Normal RUN
• Module warning RUN
(Moderate Error STOP)
• PAUSE
Send method
Select the data send method.
• Send attached file
• Send text mail
Attached file form
Set the data format for the attached
file
• Binary format
• ASCII format
• CSV format
Attached file name
Set the attached file name
—
PLC inquiry interval
Set time interval between reading the
CPU status and device values and
the units (h/min/s)
• 30 s to 24 h
Input format of inspection
value
Select the input format of the
monitoring data
• Decimal/hexadecimal
Condition device
Set the condition device
—
Condition for inspection
Set the monitoring condition
—
Monitoring value
Set the monitoring value
—
Notification data storage
device
Notification data storage device value
—
Notif. data points
Set the notification data points
—
: Setting item : Setting not required
1 When an e-mail is sent with the PLC status inspection, only subject
(PLC CPU status is stored) is sent.
(1) Condition for PLC inspection
Condition for PLC inspection
Description
Normal STOP
Sends an e-mail when the PLC CPU is placed in the STOP status normally.
Module error
Module system error
Sends an e-mail when an error that stops the CPU execution has occurred.
Module warning STOP
Sends an e-mail when the PLC CPU is stopped by an external operation,
etc. while an error that allows to continue the CPU execution has occurred.
Normal RUN
Sends an e-mail when the PLC CPU is placed in the RUN status normally.
Module warning RUN
Sends an e-mail when an error that does not allow to continue the CPU
execution has occurred while the PLC CPU is in the RUN status. (The PLC
CPU is in operation.)
PAUSE
Sends an e-mail when the PLC CPU is placed in the PAUSE status.
(2) Send method
Select the send method of the device monitoring results.
Item
Explanation
Send attached file
Sends data as an attached file in the file format designated in (3).
Send text mail
Sends data as the main text of e-mail in ASCII code format.
It is not necessary to designate items (3) and (4) when this setting is used.