MELSEC-Q
3 WHEN COMMUNICATING WITH MELSECNET/H, MELSECNET/10
RELAY
3.3.3 Routing parameter settings
The routing parameters contain information of the Ethernet modules passed through
when accessing other stations.
This section explains the routing parameters that must be set in order to access other
stations via the Ethernet module using the MELSECNET/H, MELSECNET/10 relay
communication function.
Select [GX Developer] - [Network parameters] to start the [Setting the MNET/10H
Ethernet routing information].
For details on how to display the screen, see the GX Developer Operating Manual.
Routing information setting
Item name
Description of setting
Setting range/option
Transfer to Network No.
Set the Network No. of the Ethernet or MELSECNET/H, MELSECNET/10 to which the
communication request destination station or the communication request source station is connected
when sending a communication request message or a response message, respectively.
1 to 239
Intermediate network No.
Set the Network No. of the Ethernet or MELSECNET/H, MELSECNET/10 to which the next
communication relay receive station or the next communication relay send station is connected
when sending a communication request message or a response message, respectively.
1 to 239
Intermediate station No.
Set the station number of the target Ethernet module/network module that is used as relay to the
network set by the Intermediate station No..
1 to 64