2 USING THE E-MAIL FUNCTION
(3) Attached file format
Item
Explanation
Binary format
Sends the attached file in binary format.
The Ethernet module sends the attached file as they are with the code
currently in use.
(Binary to ASCII conversion is not performed.)
ASCII format
Sends the attached file in ASCII format.
The Ethernet module converts the attached file from binary to ASCII.
CSV format
Sends the attached file in CSV format.
The Ethernet module converts the attached file from binary to CSV.
(4) Attached file name
Designate the name of an attached file. If a file name is not designated, the
Ethernet module automatically names it and sends the file named mmddhhss
(month, date, hour, minute) (same as for e-mail sending).
(5) PLC inquiry interval
Designate the interval for the Ethernet module to read the CPU status and device
values from the PLC CPU.
The user can designate any inquiry time interval (time) within the ranges shown
below.
Time unit
Setting range (default: 5 min)
h
1 to 24
min
1 to 1440
s
30 to 3600
(6) Input format of inspection value
Select the input format (decimal/hexadecimal) of the monitoring value.
(7) Condition device
Designate the device to be monitored.
POINT
(1) A maximum of 16 devices can be monitored.
(2) It is possible to designate devices that can be accessed for communication using
the MC protocol directly as condition devices (see the Reference Manual).
In this case, Timer, Retentive timer and Counter should be designated by T, ST,
or C.
The following devices cannot be designated:
• Step relay (S)
• Direct input (DX)
• Direct output (DY)
• Index qualification
• Indirect designation
(3) After completion of the news setting, the system will rearrange the condition
devices in the order; word devices first and then bit devices.
Display the news setting screen again to confirm the condition device settings.