5 - 6 5 - 6
MELSEC-Q
5 WHEN USING FILE TRANSFER FUNCTIONS (FTP SERVER)
(2) Log-in name and password (Address: 3B0
H
), (3B6
H
); Default value:
QJ71E71
(a) Set the log-in name and password for the external device to request (log-in)
file transfer to the Ethernet module in order to use the FTP server function of
the Ethernet module.
(b) If the FTP log-in name is changed and invalid characters are entered,
"QJ71E71" is set as the log-in name.
(c) If the password is changed and invalid characters are entered, "QJ71E71" is
set as the password.
(3) Command input monitoring timer (address: 3BA
H
); Default value:
1800 (0708
H
) (15 min)
(a) Set the monitoring time for the Ethernet module to monitor the command
input time from the FTP client when it operates as the FTP server.
(b) It is recommended to use the default value for this timer value as much as
possible.
When changing the setting value, determine the command input monitoring
timer value upon consulting the administrator of the external device or
system.
(c) Designate the setting value in the range of <1
H
to 7FFF
H
/1 to 32767>.
(15 min at the default value of 1800)
The FTP connection is disconnected if there is no command input from the
FTP client side within the time designated by the command input monitoring
timer value after the FTP client log-in.
When restarting the file transfer, start over from the log-in operation again.
(4) PLC monitoring timer (address: 3BB
H
); Default value: 10 (000A
H
)
(5 s)
(a) Set the monitoring time for the Ethernet module to monitor the operation of
the local station's QCPU when the Ethernet module is operating as the FTP
server.
(b) It is recommended to use the default value for this timer value as much as
possible.
When changing the setting value, determine the CPU monitoring timer value
upon consulting the system administrator.
(c) Designate the setting value in the range of <1
H
to 7FFF
H
/1 to 32767>.
The FTP connection is disconnected if an ACPU monitoring error is detected
after the FTP client log-in.
When restarting the file transfer, make sure that the local station's QCPU is
operating normally and then start over from the log-in operation again.