3 - 3 3 - 3
MELSEC-Q
3 WHEN COMMUNICATING WITH MELSECNET/H, MELSECNET/10
RELAY
(2) Accessible stations (communication request destination stations)
and relay stations (communication relay stations)
This relay communication function allows communication with PLCs of other
stations if the communication destination PLCs (communication request destination
stations) and all the relay stations to the communication destination stations
(communication relay stations) are configured with the modules listed below.
(a) Accessible PLC modules (communication request destination stations: other
stations)
1) PLC CPU modules
Model name
PLC CPU
-
Basic model
Q00JCPU, Q00CPU, Q01CPU
High performance
model
Q02CPU, Q02HCPU, Q06HCPU, Q12HCPU, Q25HCPU
Process CPU
Q12PHCPU, Q25PHCPU
QCPU
(Q mode)
Redundant CPU
Q12PRHCPU, Q25PRHCPU
PLC CPU
Q2ACPU, Q2ACPU-S1, Q2ASCPU, Q2ASCPU-S1, Q2ASHCPU, Q2ASHCPU-S1,
Q3ACPU, Q4ACPU
QnACPU
Redundant CPU
Q4ARCPU
ACPU
QCPU (A mode)
A1NCPU, A2NCPU, A2NCPU-S1, A3NCPU, A2ACPU, A2ACPU-S1, A3ACPU,
A2UCPU, A2UCPU-S1, A3UCPU, A4UCPU, A1SCPU, A1SJCPU(-S3), A1SHCPU,
A1SJHCPU, A2SCPU, A2SHCPU, A2ASCPU, A2ASCPU-S1, A0J2HCPU, Q02CPU-A,
Q02HCPU-A, Q06HCPU-A
2) Remote I/O station modules
Model name
MELSECNET/H
Remote I/O station
QJ72LP25-25, QJ72LP25GE, QJ72BR15
MELSECNET/10
Remote I/O station (
1
)
AJ72QLP25, AJ72QBR15,
A1SJ72QLP25, A1SJ72QBR15
AJ72LP25(G), AJ72BR15,
1 It is possible to read from and write to the buffer memory of special
function modules that are installed in MELSECNET/10 remote I/O stations.
(b) Modules that can act as relays between networks (communication relay stations)
Model name
MELSECNET/H
QJ71LP21, QJ71LP21-25, QJ71LP21S-25, QJ71LP21GE, QJ71BR11
(MELSECNET/H mode)
QJ71LP21, QJ71LP21-25, QJ71LP21S-25, QJ71LP21GE, QJ71BR11
(MELSECNET/10 mode)
AJ71QLP21(S/G), AJ71QBR11, A1SJ71QLP21, A1SJ71QBR11
MELSECNET/10
AJ71LP21(G), AJ71LR21, AJ71BR11, A1SJ71LP21, A1SJ71BR11
QJ71E71-100, QJ71E71-B5, QJ71E71-B2, QJ71E71
Ethernet (
2
)
AJ71QE71N-T, AJ71QE71N-B5, AJ71QE71N-B2, AJ71QE71N-B5T,
A1SJ71QE71N-T, A1SJ71QE71N-B5, A1SJ71QE71N-B2, A1SJ71QE71N-B5T,
AJ71QE71, AJ71QE71-B5, A1SJ71QE71-B2, A1SJ71QE71-B5
2 QnA series Ethernet interface modules can act as relays between
networks if the function version is B or later.
Verify the function version with the production date shown in the "Date
column of the rated plate", which is attached to the side of the module.
(Manufactured date: Year (last two digits), Month (two digits), function
version (one digit))