6 - 53 6 - 53
MELSEC-Q
6 DEDICATED INSTRUCTIONS
POINT
(1) The WRITE instruction can be executed only when the target station is the
Q/QnACPU.
(The WRITE instruction cannot be executed for an ACPU connected to the
MELSECNET/10 or Ethernet network systems.)
Thus, the target station numbers should be limited to Q/QnACPU station
numbers.
(2) When writing data from the other station CPU module device with the WRITE
instruction, specify the device within the range applicable to the host station
CPU module.
(Head device number to be write in other station CPU module (S2)) + (number
of write points -1)
< (last device number of host station CPU module )
: Last device number in host station CPU module having the same device
name as (S2).
REMARK
1) 1: When the instruction is completed, the completion status ((S1) + 1) and the
clock data ((S1) + 11 to (S1) + 17) at abnormal occurrence are stored in the
control data.
2) The number of steps for the WRITE instruction is 10.