6 DEDICATED INSTRUCTIONS
6.9 SEND Instruction
This instruction sends data to other station's Q/QnACPU.
Applicable device
Internal device
MELSECNET/H,
MELSECNET/10
Direct J \
Set
data
Bit
Word
File register
Bit
Word
Special module
U \G
Index register
Zn
Constant
K, H
Others
(S1)
—
—
(S2)
—
—
(D)
—
JP.SEND
Jn
(S1)
(S2)
(D)
Command
SEND
GP.SEND
Un
Command
SEND
[Executing
condition]
[Instruction
symbol]
(S1)
(S2)
(D)
Setting data
Set data
Description
Set by (
1
)
Data type
Jn
Network number of the local station (1 to 239, 254)
254: The network designated by the valid module during other station
access.
Binary 16 bits
Un
Start I/O signal of the local station's Ethernet module.
(00 to FE: The higher 2 digits of the 3-digit I/O signal.)
User
Character string
(S1)
Head device of the local station that stores the control data.
1
User, system
(S2)
Head device of the local station that stores the send data.
User
Device name
(D)
Local station device that is turned on for one scan by the completion of
the instruction.
(D) + 1 is turned on if the instruction execution completes abnormally.
System
Bit
The local devices and the file register for each program cannot be used as devices
used in setting data.
POINT
The SEND instruction can be executed only when the target station is a Q/QnACPU.
(The SEND instruction cannot be executed for an ACPU connected to an
MELSECNET/10 or Ethernet network system.)
REMARK
1) 1: When the instruction is completed, the completion status ((S1) + 1) and clock
data at abnormal occurrence ((S1) + 11 to (S1) + 17) are stored in the control
data.
2) The number of steps for the SEND instruction is 8.