22 -
25
22. TROUBLE SHOOTING
2113
[SP. UNIT ERROR]
Data of special function module to be simulated is
not set in the simulation date.
■
Collateral informationmmon
• Common Information:FFFF
H
(fixed)
• Individual Information:Program error location
■
Diagnostic Timing
• When instruction executed/STOP
RUN
Read the individual information of the error using a
peripheral device, and check the special function
module /special function module dedicated
instruction (network instruction) that corresponds to
the value (program error part) to make modification.
RUN:
Off/On
ERR.:
Flicker/On
CPU Status:
Stop/
Continue
*1
QnA
2210
[BOOT ERROR]
There is no boot file in the drive designated by the
parameter enabled drive switch even though the
Boot DIP switch is ON.
■
Collateral informationmmon
• Common Information:Drive name
• Individual Information:–
■
Diagnostic Timing
• At power ON/At reset
Check and correct the valid parameter drive
settings made by the DIP switches.
Set the boot file to the drive specified by the
parameter drive DIP switches.
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
2300
[ICM. OPE. ERROR]
• A memory card was removed without switching
the memory card in/out switch OFF.
• The memory card in/out switch is turned ON
although a memory card is not actually installed.
■
Collateral informationmmon
• Common Information:Drive name
• Individual Information:–
■
Diagnostic Timing
• When memory card is inserted or removed/When
memory card is inserted
• Remove memory card after placing the memory
card in/out switch OFF.
• Turn on the card insert switch after inserting a
memory card.
RUN:
Off/On
ERR.:
Flicker/On
CPU Status:
Stop/
Continue
*1
2301
[ICM. OPE. ERROR]
• The memory card has not been formatted.
• Memory card format status is incorrect.
■
Collateral informationmmon
• Common Information:Drive name
• Individual Information:–
■
Diagnostic Timing
• When memory card is inserted or removed/When
memory card is inserted
• Format memory card.
• Reformat memory card.
2302
[ICM. OPE. ERROR]
A memory card that cannot be used with the CPU
module has been installed.
■
Collateral informationmmon
• Common Information:Drive name
• Individual Information:–
■
Diagnostic Timing
• When memory card is inserted or removed
• Format memory card.
• Reformat memory card.
• Check memory card.
2400
[FILE SET ERROR]
The file designated at the PLC file settings in the
parameters cannot be found.
■
Collateral informationmmon
• Common Information:File name/Drive name
• Individual Information:Parameter number
■
Diagnostic Timing
• At power ON/At reset/
At writing to progurammable controller
• Read the individual information of the error using
peripheral device, check to be sure that the
parameter drive name and file name correspond
to the numerical values there (parameter
number), and correct.
• Create a file created using parameters, and load
it to the CPU module.
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
Error
Code
Error Contents and Cause
Corrective Action
LED Status
CPU Status
Corresponding
CPU
*1
CPU operation can be set in the parameters at error occurrence. (LED indication varies.)
Содержание Q2ACPU
Страница 1: ......
Страница 2: ......
Страница 221: ...12 12 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU ...
Страница 222: ...12 13 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU ...
Страница 237: ...12 28 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU MEMO ...
Страница 269: ...16 11 16 POWER SUPPLY MODULE 2 Names and description of parts of the A62P A62PEU and A65P module ...
Страница 271: ...16 13 16 POWER SUPPLY MODULE 4 Names and description of parts of the A66P ...
Страница 343: ...21 21 13 MAINTENANCE AND INSPECTION 21 4 2 Replacement of the fuse for an output module ...
Страница 357: ...22 12 22 TROUBLESHOOTING ...
Страница 359: ...22 14 22 TROUBLESHOOTING MEMO ...
Страница 417: ...App 20 APPENDICES 3 Shift instructions Classification Symbol Description n bit shift 1 bit shift 1 word shift ...
Страница 429: ...App 32 APPENDICES Trigonometric function Classification Symbol Description ...
Страница 432: ...App 35 APPENDICES 15 Clock instructions Classification Symbol Description Clock data read write ...
Страница 537: ...App 140 APPENDICES REMARK 1 Message 1 An error code is displayed in 2 Alert 1 3 Alert 2 ...
Страница 538: ...App 141 APPENDICES APPENDIX 6 EXTERNAL DIMENSIONS Appendix 6 1 CPU Module 1 Q3ACPU Q4ACPU modules Unit mm inch ...
Страница 539: ...App 142 APPENDICES 2 Q2ACPU Q2ACPU S1 modules Unit mm inch ...
Страница 541: ...App 144 APPENDICES 2 A66P power supply module Unit mm inch ...
Страница 542: ...App 145 APPENDICES Appendix 6 3 Main Base Unit 1 A32B base unit 2 A32B S1 base unit Unit mm inch Unit mm inch ...
Страница 543: ...App 146 APPENDICES 3 A35B base unit 4 A38B A38HB A38HBEU base unit Unit mm inch Unit mm inch ...
Страница 567: ...MEMO ...
Страница 569: ......
Страница 570: ......