20. EMC AND LOW VOLTAGE DIRECTIVES
(2) MELSECNET (II) and MELSECNET/10 modules
(a) Use double-shielded coaxial cables (MITSUBISHI CABLE INDUSTRIES, LTD.:
5C-2V-CCY) for the MELSECNET modules (such as AJ71AR21, AJ71QBR11)
which uses coaxial cables. Radiated noise in the range of 30 MHz or higher can
be suppressed by using double-shielded coaxial cables. Ground the double-
shielded coaxial cable by connecting its outer shield to the ground.
Refer to (1) for grounding of the shield.
(b) Always attach a ferrite core to the double-shielded coaxial cable connected to
the MELSECNET module. In addition, position the ferrite core on each cable
near the outlet of the control panel. The ZCAT3035 ferrite core (TDK) is
recommended.
(3) Ethernet module
Precautions to be followed when AUI cables
*1
, twisted pair cables and coaxial cables
are used are described below.
(a) Be sure to ground the AUI cables connected to the 10BASE5
connectors.Because the AUI cable is of the shielded type, as shown in the figure
below, partly remove the outer sheath, and ground the exposed shield section to
the widest possible surface.
Refer to (1) for the grounding of the shield.
(b) Use shielded twisted pair cables as the twisted pair cables
*1
connected to the
10BASE-T connectors. Partly strip the outer sheath of the shielded twisted pair
cable, and ground the exposed shield section to the widest possible area as
shown below.
Refer to (1) for the grounding of the shield.
*1
Make sure to attach a ferrite core to the cable.
As a ferrite core, the ZCAT2035 manufactured by TDK is recommended.
AUI cable
Shield
Shielded twisted pair cable
Shield
Содержание Q2ACPU
Страница 1: ......
Страница 2: ......
Страница 221: ...12 12 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU ...
Страница 222: ...12 13 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU ...
Страница 237: ...12 28 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU MEMO ...
Страница 269: ...16 11 16 POWER SUPPLY MODULE 2 Names and description of parts of the A62P A62PEU and A65P module ...
Страница 271: ...16 13 16 POWER SUPPLY MODULE 4 Names and description of parts of the A66P ...
Страница 343: ...21 21 13 MAINTENANCE AND INSPECTION 21 4 2 Replacement of the fuse for an output module ...
Страница 357: ...22 12 22 TROUBLESHOOTING ...
Страница 359: ...22 14 22 TROUBLESHOOTING MEMO ...
Страница 417: ...App 20 APPENDICES 3 Shift instructions Classification Symbol Description n bit shift 1 bit shift 1 word shift ...
Страница 429: ...App 32 APPENDICES Trigonometric function Classification Symbol Description ...
Страница 432: ...App 35 APPENDICES 15 Clock instructions Classification Symbol Description Clock data read write ...
Страница 537: ...App 140 APPENDICES REMARK 1 Message 1 An error code is displayed in 2 Alert 1 3 Alert 2 ...
Страница 538: ...App 141 APPENDICES APPENDIX 6 EXTERNAL DIMENSIONS Appendix 6 1 CPU Module 1 Q3ACPU Q4ACPU modules Unit mm inch ...
Страница 539: ...App 142 APPENDICES 2 Q2ACPU Q2ACPU S1 modules Unit mm inch ...
Страница 541: ...App 144 APPENDICES 2 A66P power supply module Unit mm inch ...
Страница 542: ...App 145 APPENDICES Appendix 6 3 Main Base Unit 1 A32B base unit 2 A32B S1 base unit Unit mm inch Unit mm inch ...
Страница 543: ...App 146 APPENDICES 3 A35B base unit 4 A38B A38HB A38HBEU base unit Unit mm inch Unit mm inch ...
Страница 567: ...MEMO ...
Страница 569: ......
Страница 570: ......