App -
65
APPENDICES
Table App. 2.10. Special relay
ACPU
Special
Relay
Special
Relay after
Conversion
Special
Relay for
Modification
Name
Meaning
Details
Corresponding
CPU
M9235
SM1235
–
Local station,
remote I/O station
parameter error
detect status
OFF : No errors
ON
: Error detection
Depends on whether or not a local or a remote I/O station
has detected any link parameter error in the master station
QnA
M9236
SM1236
–
Local station,
remote I/O station
initial
communications
status
OFF : No communications
ON
: Communications
underway
Depends on the results of initial communication between a
local or remote I/O station and the master station.
(Parameter communication, etc.)
QnA
M9237
SM1237
–
Local station,
remote I/O station
error
OFF : Normal
ON
: Abnormal
Depends on the error condition of a local or remote I/O
station.
QnA
M9238
SM1238
–
Local station,
remote I/O station
forward or reverse
loop error
OFF : Normal
ON
: Abnormal
Depends on the error condition of the forward and reverse
loop lines of a local or a remote I/O station.
QnA
M9240
SM1240
–
Link status
OFF : Online
ON
: Offline, station-to-
stationtest, or self-
loopback test
Depends on whether the local station is online or offline, or is
in station-to-station test or self-loopback test mode.
QnA
M9241
SM1241
–
Forward loop line
error
OFF : Normal
ON
: Abnormal
Depends on the error condition of the forward loop line.
QnA
M9242
SM1242
–
Reverse loop line
error
OFF : Normal
ON
: Abnormal
Depends on the error condition of the reverse loop line.
QnA
M9243
SM1243
–
Loopback
implementation
OFF : Loopback not being
conducted
ON
: Loopback
implementation
Depends on whether or not loopback is occurring at the local
station.
QnA
M9246
SM1246
–
Data not received
OFF : Reception
ON
: No reception
Depends on whether or not data has been received from the
master station.
QnA
M9247
SM1247
–
Data not received
OFF : Reception
ON
: No reception
Depends on whether or not a tier three station has received
data from its master station in a three-tier system.
QnA
M9250
SM1250
–
Parameters not
received
OFF : Reception
ON
: No reception
Depends on whether or not link parameters have been
received from the master station.
QnA
M9251
SM1251
–
Link relay
OFF : Normal
ON
: Abnormal
Depands on the data link condition at the local station.
QnA
M9252
SM1252
–
Loop test status
OFF : Not being executed
ON
: Forward or reverse
loop test execution
underway
Depends on whether or not the local station is executing a
forward or a reverse loop test.
QnA
M9253
SM1253
–
Master station
operation status
OFF : RUN or STEP RUN
status
ON
: STOP or PAUSE
status
Control is performed depending on whether the master
station is in the STOP or PAUSE mode.
QnA
M9254
SM1254
–
Local station other
than host station
operation status
OFF : RUN or STEP RUN
status
ON
: STOP or PAUSE
status
Control is performed depending on whether a local station
other than the host is in the STOP or PAUSE mode.
QnA
M9255
SM1255
–
Local station other
than host station
error
OFF : Normal
ON
: Abnormal
Depends on whether or not a local station other than the host
is in error.
QnA
Содержание Q2ACPU
Страница 1: ......
Страница 2: ......
Страница 221: ...12 12 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU ...
Страница 222: ...12 13 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU ...
Страница 237: ...12 28 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU MEMO ...
Страница 269: ...16 11 16 POWER SUPPLY MODULE 2 Names and description of parts of the A62P A62PEU and A65P module ...
Страница 271: ...16 13 16 POWER SUPPLY MODULE 4 Names and description of parts of the A66P ...
Страница 343: ...21 21 13 MAINTENANCE AND INSPECTION 21 4 2 Replacement of the fuse for an output module ...
Страница 357: ...22 12 22 TROUBLESHOOTING ...
Страница 359: ...22 14 22 TROUBLESHOOTING MEMO ...
Страница 417: ...App 20 APPENDICES 3 Shift instructions Classification Symbol Description n bit shift 1 bit shift 1 word shift ...
Страница 429: ...App 32 APPENDICES Trigonometric function Classification Symbol Description ...
Страница 432: ...App 35 APPENDICES 15 Clock instructions Classification Symbol Description Clock data read write ...
Страница 537: ...App 140 APPENDICES REMARK 1 Message 1 An error code is displayed in 2 Alert 1 3 Alert 2 ...
Страница 538: ...App 141 APPENDICES APPENDIX 6 EXTERNAL DIMENSIONS Appendix 6 1 CPU Module 1 Q3ACPU Q4ACPU modules Unit mm inch ...
Страница 539: ...App 142 APPENDICES 2 Q2ACPU Q2ACPU S1 modules Unit mm inch ...
Страница 541: ...App 144 APPENDICES 2 A66P power supply module Unit mm inch ...
Страница 542: ...App 145 APPENDICES Appendix 6 3 Main Base Unit 1 A32B base unit 2 A32B S1 base unit Unit mm inch Unit mm inch ...
Страница 543: ...App 146 APPENDICES 3 A35B base unit 4 A38B A38HB A38HBEU base unit Unit mm inch Unit mm inch ...
Страница 567: ...MEMO ...
Страница 569: ......
Страница 570: ......