7 -
9
7.
AUTO REFRESH FUNCTION
(1) Settings for auto refresh
The Table 7.1 shows the setting items for auto refresh parameters of the QnACPU.
*
Only when the file register is set to "Use the designated file" with the "Parameter", R and ZR
can be used as the auto refresh devices.
When "Use same file name as program" is set, R and ZR cannot be used.
REMARK
Table 7.1 List of auto refresh settings
Item
Description
Setting range
Setting station
M
L
T
Number of modules
The number of CC-Link modules is set.
1 to 8
Module head I/O number
The head I/O number of a CC-Link module is set.
0000
H
to 0FE0
H
Module type
The loaded CC-Link module type (Master station, local station, stand-by station)
is set.
• M: Master station
• L: Local station
• T: Stand-by station
Receiving data batch refresh
bit device
(Input data)
• The device that stores the batch refresh received data from the remote station
is set.
• When the head device number is set, the points corresponding to the specified
number of stations (Total number of stations) are obtained to refresh all areas.
The output module area is also refreshed.
• The settings are made in units of 16 points.
X, M, L, B, T, ST, C, D,
W, R, ZR
*
Transmission data batch
refresh bit device
(Output data)
• The device that stores the batch refresh send data to the remote station is set.
• When the head device number is set, the points corresponding to the specified
number of stations (Total number of stations) are obtained to refresh all areas.
The input module area is also refreshed.
• The settings are made in units of 16 points.
X, M, L, B, T, ST, C, D,
W, R, ZR
*
Receiving data batch refresh
word device
(Remote device: RWr)
• The device that stores the batch refresh received data from the remote station
is set.
• When the head device number is set, the points corresponding to the specified
number of stations (Total number of stations) are obtained to refresh all areas.
The I/O module area is also refreshed.
• The settings are made per point.
M, L, B, T ,ST, C, D, W,
R, ZR
*
Transmission data batch
refresh device
(Remote device: RWw)
• The device that stores the batch refresh send data to the remote station is set.
• When the head device number is set, the points corresponding to the specified
number of stations (Total number of stations) are obtained to refresh all areas.
The I/O module area is also refreshed.
• The settings are made per point.
M, L, B, T ,ST, C, D, W,
R, ZR
*
Receiving buffer specification
for transient station
• The receive buffer capacity for transient station is set.
80 to 4096
Transmission buffer
specification for transient
station
• The send buffer capacity for transient station is set.
80 to 4096
Batch refresh device for
special relay
• The destination device for special relay is set.
M, L, B, T ,ST, C, D, W,
R, ZR
*
1) In "Setting station" in the table above, M refers to the master station, L to the
local station, and T to the stand-by station.
2) In the table above, means that the setting can be made and means that
the setting is not required.
Содержание Q2ACPU
Страница 1: ......
Страница 2: ......
Страница 221: ...12 12 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU ...
Страница 222: ...12 13 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU ...
Страница 237: ...12 28 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU MEMO ...
Страница 269: ...16 11 16 POWER SUPPLY MODULE 2 Names and description of parts of the A62P A62PEU and A65P module ...
Страница 271: ...16 13 16 POWER SUPPLY MODULE 4 Names and description of parts of the A66P ...
Страница 343: ...21 21 13 MAINTENANCE AND INSPECTION 21 4 2 Replacement of the fuse for an output module ...
Страница 357: ...22 12 22 TROUBLESHOOTING ...
Страница 359: ...22 14 22 TROUBLESHOOTING MEMO ...
Страница 417: ...App 20 APPENDICES 3 Shift instructions Classification Symbol Description n bit shift 1 bit shift 1 word shift ...
Страница 429: ...App 32 APPENDICES Trigonometric function Classification Symbol Description ...
Страница 432: ...App 35 APPENDICES 15 Clock instructions Classification Symbol Description Clock data read write ...
Страница 537: ...App 140 APPENDICES REMARK 1 Message 1 An error code is displayed in 2 Alert 1 3 Alert 2 ...
Страница 538: ...App 141 APPENDICES APPENDIX 6 EXTERNAL DIMENSIONS Appendix 6 1 CPU Module 1 Q3ACPU Q4ACPU modules Unit mm inch ...
Страница 539: ...App 142 APPENDICES 2 Q2ACPU Q2ACPU S1 modules Unit mm inch ...
Страница 541: ...App 144 APPENDICES 2 A66P power supply module Unit mm inch ...
Страница 542: ...App 145 APPENDICES Appendix 6 3 Main Base Unit 1 A32B base unit 2 A32B S1 base unit Unit mm inch Unit mm inch ...
Страница 543: ...App 146 APPENDICES 3 A35B base unit 4 A38B A38HB A38HBEU base unit Unit mm inch Unit mm inch ...
Страница 567: ...MEMO ...