App -
59
APPENDICES
(9) A to QnA conversion correspondences
Special relays SM1000 to SM1255 are the relays which correspond to ACPU special
relays M9000 to M9255 after A to QnA conversion.
These special relays are all set by the system, and cannot be set by the user
program.
To turn them ON/OFF by the user program, change the special relays in the program
into those of QnACPU.
However, some of SM1084 and SM1200 to SM1255 (corresponding to M9084 and
M9200 to M9255 before conversion) can be turned ON/OFF by the user program, if
they could be turned ON/OFF by the user program before conversion.For details on
the ACPU special relays, see the user's manuals for the individual CPUs, and
MELSECNET or MELSECNET/B Data Link System Reference Manuals
The following are additional explanations about the Special Relay for Modification
column.
When a special relay for modification is provided, the device number should
be changed to the provided QnACPU special relay.
When
is provided, the converted special relay can be used for the device
number.
When
is provided, the device number does not work with QnACPU.
Table App. 2.10. Special relay
ACPU
Special
Relay
Special
Relay after
Conversion
Special
Relay for
Modification
Name
Meaning
Details
Corresponding
CPU
M9000
SM1000
–
Fuse blown
OFF : Normal
ON
: Module with blown
fuse
• Turned on when there is one or more output modules of
which fuse has been blown.
• Remains ON if the condition is restored to normal
thereafter.
• Output modules of remote I/O stations are also checked
fore fuse condition.
QnA
M9002
SM1002
–
I/O module verify
error
OFF : Normal
ON
: Error
• Turned on if the status of I/O module is different form
entered status when power is turned on.
• Remains ON if the condition is restored to normal
thereafter.
• I/O module verification is done also to remote I/O station
modules.
• Reset is enabled only when special registers SD1116 to
SD1123 are reset.
QnA
M9004
SM1004
–
NIMI link master
module error
OFF : Normal
ON
: Error
• Goes ON if MINI (S3) link error is detected at even one of
the installed AJ71PT32 (S3) modules.
• Remains ON if the condition is restored to normal
thereafter.
QnA
M9005
SM1005
––
AC DOWN
detection
OFF : AC DOWN not
detected
ON
: AC DOWN detected
• Turns ON if an instantaneous power failure of within 20ms
occurs during use of the AC power supply module.
• Reset when the power supply is switched OFF, then ON.
QnA
• Turns ON if an instantaneous power failure of within 1ms
occurs during use of the DC power supply module.
• Reset when the power supply is switched OFF, then ON.
QnA
M9006
SM1006
–
Battery low
OFF : Normal
ON
: Battery low
• Turns ON when the battery voltage drops to or below the
specified.
• Turns OFF when the battery voltage returns to normal
thereafter.
QnA
M9007
SM1007
–
Battery low latch
OFF : Normal
ON
: Battery low
• Turns ON when the battery voltage drops to or below the
specified.
• Remains ON if the battery voltage returns to normal
thereafter.
QnA
M9008
SM1008
SM1
Self-diagnosis
error
OFF : No error
ON
: Error
• Turned on when error is found as a result of self-
diagnosis.
QnA
M9009
SM1009
SM62
Annunciator
detection
OFF : No F number detected
ON
: F number detected
• Turned on when OUT F of SET F instruction is
executed.
• Switched off when SD1124 data is cleared to zero.
QnA
Содержание Q2ACPU
Страница 1: ......
Страница 2: ......
Страница 221: ...12 12 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU ...
Страница 222: ...12 13 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU ...
Страница 237: ...12 28 12 OVERVIEW OF PROCESSING PERFORMED BY THE QnACPU MEMO ...
Страница 269: ...16 11 16 POWER SUPPLY MODULE 2 Names and description of parts of the A62P A62PEU and A65P module ...
Страница 271: ...16 13 16 POWER SUPPLY MODULE 4 Names and description of parts of the A66P ...
Страница 343: ...21 21 13 MAINTENANCE AND INSPECTION 21 4 2 Replacement of the fuse for an output module ...
Страница 357: ...22 12 22 TROUBLESHOOTING ...
Страница 359: ...22 14 22 TROUBLESHOOTING MEMO ...
Страница 417: ...App 20 APPENDICES 3 Shift instructions Classification Symbol Description n bit shift 1 bit shift 1 word shift ...
Страница 429: ...App 32 APPENDICES Trigonometric function Classification Symbol Description ...
Страница 432: ...App 35 APPENDICES 15 Clock instructions Classification Symbol Description Clock data read write ...
Страница 537: ...App 140 APPENDICES REMARK 1 Message 1 An error code is displayed in 2 Alert 1 3 Alert 2 ...
Страница 538: ...App 141 APPENDICES APPENDIX 6 EXTERNAL DIMENSIONS Appendix 6 1 CPU Module 1 Q3ACPU Q4ACPU modules Unit mm inch ...
Страница 539: ...App 142 APPENDICES 2 Q2ACPU Q2ACPU S1 modules Unit mm inch ...
Страница 541: ...App 144 APPENDICES 2 A66P power supply module Unit mm inch ...
Страница 542: ...App 145 APPENDICES Appendix 6 3 Main Base Unit 1 A32B base unit 2 A32B S1 base unit Unit mm inch Unit mm inch ...
Страница 543: ...App 146 APPENDICES 3 A35B base unit 4 A38B A38HB A38HBEU base unit Unit mm inch Unit mm inch ...
Страница 567: ...MEMO ...
Страница 569: ......
Страница 570: ......