Chapter 12
95
Technical data
Occurrence
In1: Digital inputs
Out1: Digital outputs
General
C4000 response time
14.0 ms Robot response time
40.0 ms
General
Input processing time
6.5 ms Output processing time
4.5 ms
When On/Off filter
8.0 ms
–
When X1 … X8 is
connected at the test
output
a) Safety mats and
bumpers
b) Testable sensors Type 4
(e.g. L41)
c) All other sensors
–
–
–
–
Total In1
20.5 ms
Total Out1
44.5 ms
Evaluation
1. Inputs
Response time of the considered input in the
signal path (path 1)
In1
20.5 ms
2. Logic
Response time of the logic
2 × logic execution time
8.0 ms
Delay through logic application
–
3. Outputs
Response time of the considered output in
the signal path (path 1)
Out1
44.5 ms
Total response time
73.0 ms
Table 54: Example for the calculation of the response time of path 1 of a MELSEC-WS safety controller
Occurrence
In2: Input from EFI device
Occurrence
Out1: Digital outputs
If EFI functions are used
via SICK EFI-compatible
devices
Response time of the
EFI data source
(C4000 receiver
(stand-alone))
12.0 ms
General Robot
response
time
40.0
ms
Constant (C4000)
1.5 ms
General
Output processing time
4.5 ms
Total In2
13.5 ms
Total Out1
44.5 ms
Evaluation
1. Inputs
Response time of the considered input in the
signal path (path 2)
In2
13.5 ms
2. Logic
Response time of the logic
2 × logic execution time
8.0 ms
Delay through logic application
–
3. Outputs
Response time of the considered output in
the signal path (path 2)
Out1
44.5 ms
Total response time
66.0 ms
Table 55:
Example for the calculation of the response time of path 2 of a MELSEC-WS safety controller
Figure 30:
Response times within a
MELSEC-WS safety
controller
Содержание MELSEC-WS series
Страница 1: ...Safety Controller User s Manual WS0 CPU0 WS0 CPU1 WS0 CPU3 WS0 XTDI WS0 XTIO WS0 4RO ...
Страница 2: ......
Страница 20: ...Chapter 1 17 About this document visible or invisible radiation a combination of several risks and hazards ...
Страница 117: ...Chapter 14 114 Annex ...
Страница 134: ...Chapter 14 131 Annex ...
Страница 151: ......