99
Technical data
WS0-CPU0
WS0-CPU1/3
Cross-section of connecting wires
Single-core or finely stranded:
1 × 0.14 … 2.5 mm² (26 to 13 AWG) or 2 × 0.14 …
0.75 mm² (26 to 18 AWG)
Finely stranded with ferrules
1 × 0.25 … 2.5 mm² (23 to 13 AWG) or 2 × 0.25 …
0.5 mm² (23 to 20 AWG)
EFI connection method, Flexi Line
connection method
–
Dual level spring clamp
terminals
Cross-section of EFI connecting
wires
–
Single-core or finely
stranded:
1 × 0.2…1.5 mm² (24 to
15 AWG)
Finely stranded with
ferrules:
1 × 0.25…1.5 mm² (23 to
15 AWG)
Dimensions (W × H × D)
22.5 × 96.5 × 120.8 mm
22.5 × 101.7 × 120.8 mm
Weight
111 g (± 5%)
CPU1 : 119 g (± 5%)
CPU3 : 133 g (± 5%)
Power supply (A1, A2) via memory plug WS0-MPL0 or WS0-MPL1
Supply voltage
24 V DC (16.8 … 30 V DC)
Supply voltage UL/CSA applications 24 V DC
Type of supply voltage
PELV or SELV
The current of the power supply unit for the CPU
module has to be limited to a maximum of 4 A –
either by the power supply unit itself or by a fuse
Overvoltage category
II (EN 61131-2)
Power consumption
Max. 2.5 W
Switch-on time
Max. 18 s