Chapter 10
83
Diagnostics
LED indication on module
Possible error
codes
Possible reasons
Possible measures
CPU module
(WS0-CPU0, WS0-
CPU1 or WS0-CPU3)
Safety I/O module
(WS0-XTIO or
WS0-XTDI)
MS =
Green
One or more safety
I/O modules :
MS =
Red/green
(1 Hz) (firmware
≥
V2.00.0)
or
MS =
Red (1 Hz)
(firmware V1.xx.0) and
Q1 or Q2 or Q3 or Q4
=
Green (1 Hz)
WS0-XTIO:
0x4701,
0x4702,
0x4704,
0x4705.
Short circuit to 24 V or cross circuit in
wiring of safe output Q1…Q4 (whose
LED is flashing).
Capacitive load exceeded the
allowed maximum value (e.g. by
capacitor for spark quenching).
Inductive load exceeded the
maximum value allowed
Internal Hardware failure of WS0-
XTIO module
Short circuit to 0 V in wiring of
safety output Q1…Q4 (whose LED
is flashing).
Power supply on the XTIO module
interrupted briefly
Check wiring of all output.
Check
capacitive
load.
Check inductive load.
Replace XTIO module.
To reset the error all outputs of the
effected module have to be turned off
from logic of by turning off related input
signals, e.g. E-stop. Error reset can
take up to 8 seconds. Alternatively
power cycle the CPU module.
One or more safety
I/O modules :
MS =
Red/green
(1 Hz) (firmware
≥
V2.00.0)
or
MS =
Red (1 Hz)
(firmware V1.xx.0)
and
I1 or I2 or I3 or I4 or I5
or I6 or I7 or I8 =
Green (1 Hz)
WS0-XTIO/
WS0-XTDI:
0x4601
For inputs which are connected to test
output:
Short circuit to 24 V or cross circuit
in wiring for tested sensors:
a) Short circuit to 24 V or cross
circuit in wiring from X1, X2,…or
X8 to tactile switch or test input
of testable input.
b) Short circuit to 24 V or cross
circuit in wiring from tactile
switch or output of testable
sensor to I1, I2,…or I8.
Defect
testable
sensor.
Cable interruption in wiring for
safety mat:
a) Cable interruption in wiring from
X1, X2,…or X8 to safety mat.
b) Cable interruption in wiring from
safety mat to I1, I2,…or I8.
Defect safety mat.
Check wiring of effected input.
Replace
testable
sensor.
To reset the error turn off the effected
input (input state Low/Low for
equivalent dual channel inputs,
Low/High for complementary dual
channel inputs) or power cycle the
CPU module.
Содержание MELSEC-WS series
Страница 1: ...Safety Controller User s Manual WS0 CPU0 WS0 CPU1 WS0 CPU3 WS0 XTDI WS0 XTIO WS0 4RO ...
Страница 2: ......
Страница 20: ...Chapter 1 17 About this document visible or invisible radiation a combination of several risks and hazards ...
Страница 117: ...Chapter 14 114 Annex ...
Страница 134: ...Chapter 14 131 Annex ...
Страница 151: ......