Chapter 10
79
Diagnostics
10
Diagnostics
10.1 In the event of faults or errors
Cease operation if the cause of the malfunction has not been clearly identified!
Stop the machine if you cannot clearly identify or allocate the error and if you cannot
safely remedy the malfunction.
Complete functional test after remedying malfunction!
Carry out a full functional test after a malfunction has been remedied.
10.1.1
ERROR operating states
With certain malfunctions or a faulty configuration, the MELSEC-WS safety controller
enters the safe status. The LEDs of the individual modules of the safety controller
indicate the corresponding error level.
Depending on the error there are different error levels:
Configuration error
The system will be in state Configuration required (MS LED Red (1Hz)).
Applications in all modules are in operating state
“
Stop
”
.
All safe outputs in the system are switched off.
All safety process data is set to zero. Typically also not safety related process data
is set to zero.
Recoverable error
Applications in all modules remain in operating state Run (MS LED of the effected
modules = Red/green alternating (1 Hz), MS LED of not effected modules =
Green).
If safe outputs on the system are effected, then as a minimum these outputs are
switched off.
If safe inputs are effected, then at least the process data for these safe inputs are
set to zero.
Critical fault
The system will be in state Critical fault (MS LED of the module which detected the
critical fault = Red (2 Hz). MS LED of the modules which are unclear about the
error origin =
Red).
Applications in all modules are in operating state ‘Stop’.
All safe outputs in the system are switched off.
All safety process data is set to zero. Typically also not safety related process data
is set to zero.
ATTENTION
Содержание MELSEC-WS series
Страница 1: ...Safety Controller User s Manual WS0 CPU0 WS0 CPU1 WS0 CPU3 WS0 XTDI WS0 XTIO WS0 4RO ...
Страница 2: ......
Страница 20: ...Chapter 1 17 About this document visible or invisible radiation a combination of several risks and hazards ...
Страница 117: ...Chapter 14 114 Annex ...
Страница 134: ...Chapter 14 131 Annex ...
Страница 151: ......