Chapter 3
39
Product description
How to activate the option for switching loads with high capacitance on output
Q1 to Q4 on the WS0-XTIO:
Connect an output element to the WS0-XTIO module.
Double-click the output element using the left mouse button.
Select the
Enable switching extended capacitive loads with this output
option.
Note the increased error detection time!
Activating the option for switching loads with high capacitance increases the error
detection time. This applies primarily to single-channel outputs.
See also Section 3.8.6.
3.8.6
Single channel usage of WS0-XTIO outputs
Take into account possible brief switching to high on signal-channel outputs!
In the case of an internal hardware fault outputs Q1 to Q4.which would normally be
low, may briefly switch to high until the fault is detected. and there is a response to the
fault. The fault detection time plus the fault reaction time is dependent on the
configuration selected for the output.
WS0-XTIO firmware
version
Activation of the switching of
loads with high capacitance
Error detection time +
error response time
≤
V2.xx
Not possible
≤
10 ms
≥
V3.10
Deactivated
≤
10 ms
Activated
≤
50 ms
Take into account this aspect in your risk analysis and risk reduction strategy, above
all for single-channel outputs. Otherwise the operator of the machine will be in danger.
ATTENTION
ATTENTION
Содержание MELSEC-WS series
Страница 1: ...Safety Controller User s Manual WS0 CPU0 WS0 CPU1 WS0 CPU3 WS0 XTDI WS0 XTIO WS0 4RO ...
Страница 2: ......
Страница 20: ...Chapter 1 17 About this document visible or invisible radiation a combination of several risks and hazards ...
Страница 117: ...Chapter 14 114 Annex ...
Страница 134: ...Chapter 14 131 Annex ...
Страница 151: ......